Mitsubishi Electric CITY MULTI PUMY-P112VKM6 Service Manual page 100

Advertisement

8-10. Outdoor unit information display
SW1
Contents
setting
No. 12345678
0
00000000 Relay output (at
normal state)
Error code (at
abnormal state)
1
10000000 Indoor unit check
status
2
01000000 Protection input
3
11000000 Protection input
4
00100000 Protection input
5
10100000 Abnormality delay
display 1
6
01100000 Abnormality delay
display 2
7
11100000 Abnormality delay
display 3
8
00010000 Abnormality delay
history 1
9
10010000 Abnormality delay
history 2
10
01010000 Abnormality delay
history 3
11
11010000 Abnormality code
history 1 (the
latest)
12
00110000 Abnormality code
history 2
13
10110000 Abnormality code
history 3
14
01110000 Abnormality code
history 4
15
11110000 Abnormality code
history 5
16
00001000 Abnormality code
history 6
17
10001000 Abnormality code
history 7
18
01001000 Abnormality code
history 8
19
11001000 Abnormality code
history 9
20
00101000 Abnormality code
history 10 (the
oldest)
21
10101000 Cumulative time
22
01101000 Cumulative time
23
11101000 Outdoor unit oper-
ation display
OCH790 _100
1
2
3
Compressor
52C
21S4
operation
0000–9999 (Alternating display of addresses and error code)
Note: When abnormality occurs, check display.
No.1 unit
No.2 unit
No.3 unit
check
check
check
Note: Light on at time of abnormality
High pressure
Superheat
Compressor
abnormality
due to low
shell tem-
discharge
perature
temperature
abnormality
Note: Display detected microprocessor protection or abnormality
Heat sink
Compressor
Voltage
overheating
over current
abnormality
interception
Note: Display detected microprocessor protection or abnormality
Abnormality
Address
Indoor unit
in the number
double setting
capacity error
of indoor units
abnormality
Note: Display detected microprocessor protection or abnormality
High pressure
Superheat
Compressor
abnormality
due to low
shell tem-
delay
discharge
perature
temperature
abnormality
delay
delay
Note: Display all abnormalities remaining in abnormality delay
Heat sink
Compressor
Voltage
overheating
over current
abnormality
delay
interception
delay
delay
Note: Display all abnormalities remaining in abnormality delay
63LS
TH2 abnor-
4-way valve
abnormality
mality delay
abnormality
delay
delay
Note: Display all abnormalities remaining in abnormality delay
High pressure
Superheat
Compressor
abnormality
due to low
shell tem-
delay
discharge
perature
temperature
abnormality
delay
delay
Note: Display all abnormalities remaining in abnormality delay
Heat sink
Compressor
Voltage
overheating
over current
abnormality
delay
interception
delay
delay
Note: Display all abnormalities remaining in abnormality delay
63LS
TH2 abnor-
4-way valve
abnormality
mality delay
abnormality
delay
delay
Note: Display all abnormalities remaining in abnormality delay
Alternating display of addresses 0000–9999 and abnormality code (including abnormality delay code)
Followings are the delay code and the details of the abnormal delay
1202: Discharge/Comp. temperature, Thermistor <Compressor>(TH4)
1205: Thermistor <Outdoor liquid pipe> (TH3)
1211: Thermistor <Suction pipe> (TH6)
1214: Thermistor <Heat sink> (TH8)
1221: Thermistor <Ambient> (TH7)
1222: Thermistor <HIC> (TH2)
1400: Low pressure sensor
1402: High pressure (63H), High pressure sensor (63HS)
1600: Discharge superheat (SHd), Over charge refrigerant
1601: Insufficient refrigerant, Closed cooling valve
1608: 4-way valve disconnection
4310: Current sensor open/short
4320: Undervoltage, overvoltage, or power module
4330: Heat sink temperature
4350: Power module
4500: Outdoor fan motor
Notes:
• Display abnormalities up to present (including abnormality terminals)
• History record in 1 is the latest; records become older in sequence; history record in 10 is the oldest.
0–9999 (unit: 1 hour)
Note: Display of cumulative compressor operating time
0–9999 (unit: 10 hours)
Note: Display of cumulative compressor operating time
Compressor
Compressor
Compressor
energizing
operating
in operation
prohibition
LED1, 2
4
5
6
SV1
(SV2)
No.4 unit
No.5 unit
No.6 unit
check
check
check
TH4 abnor-
TH3 abnor-
Outdoor fan
mality
mality
rotation
frequency
abnormality
Insufficient
Current
63LS
refrigerant
sensor/
abnormality
amount
primary
abnormality
current abnor-
mality
Over capacity Indoor unit
Outdoor unit
address error
address error
TH4 abnor-
TH3 abnor-
Outdoor fan
mality delay
mality delay
rotation
frequency
abnormality
delay
Insufficient
Current
63LS
refrigerant
sensor/
abnormality
amount
primary
delay
abnormality
current abnor-
delay
mality delay
Delay caused
Power
TH6 abnor-
by closed
module
mality delay
valve in
abnormality
cooling mode
delay
TH4 abnor-
TH3 abnor-
Outdoor fan
mality delay
mality delay
rotation
frequency
abnormality
delay
Insufficient
Current
63LS
refrigerant
sensor/
abnormality
amount
primary
delay
abnormality
current abnor-
delay
mality delay
Delay caused
Power
TH6 abnor-
by closed
module
mality delay
valve in
abnormality
cooling mode
delay
Abnormality
detection
SW: setting
0: OFF
1: ON
7
8
Always
lighting
No.7 unit
No.8 unit
check
check
TH7 abnor-
TH8 abnor-
mality
mality
63HS
start over
abnormality
current
interception
abnormality
delay
Current
Serial
sensor open/
communica-
short
tion abnor-
mality
(outdoor unit)
TH7 abnor-
TH8 abnor-
mality delay
mality delay
63HS
start over
abnormality
current
delay
interception
abnormality
delay
Current
sensor open/
short delay
TH7 abnor-
TH8 abnor-
mality delay
mality delay
63HS
start over
abnormality
current
delay
interception
abnormality
delay
Current
sensor open/
short delay