5-1. Selection of indoor and outdoor units
5-1-1. Cooling
Outdoor dry bulb temperature
Total cooling load
Room 1
Indoor dry bulb temperature
Indoor wet bulb temperature
Cooling load
Room 2
Indoor dry bulb temperature
Indoor wet bulb temperature
Cooling load
Other
Indoor/Outdoor piping equivalent length
Capacity of indoor unit
P·FY series
Model class of indoor unit
Model capacity (kW)
M series
Model class of indoor unit
S series
Model capacity (kW)
P series
■ Cooling calculation
• Tentative selection of indoor units
Room1: PEFY-P50
Room2: PEFY-P71
In this case, the total capacity is 13.6. (5.6 + 8.0 = 13.6)
• Tentative selection of outdoor unit
Proper outdoor unit in this case is P125 as the total capacity of the indoor units is 13.6.
PUMY-P125
• Calculation for the corrected capacity of the total indoor units (CTi)
Correction factor for indoor design wet bulb temperature: Room 1 (20°C)
CTi = Σ (Rated capacity of indoor unit × Correction factor for indoor temperature)
= 5.6 × 1.03 + 8.0 × 0.94
= 13.3 kW
• Calculation for the corrected capacity of the outdoor unit (CTo)
Correction factor for outdoor temperature (39°C)
Correction factor for piping length (60 m)
CTo = Rated capacity of outdoor unit × Correction factor for outdoor temperature × Correction factor for piping length
= 14.0 × 0.92 × 0.88
= 11.3 kW
• Determination of maximum system capacity (CTx)
Comparison between CTi and CTo:
CTi = 13.3 > CTo = 11.3, thus, select CTo.
CTx = CTo = 11.3 kW
• Comparison with essential load
Against the essential load 10.6 kW, the maximum system capacity is 11.3 kW: A proper outdoor unit is selected.
• Calculation for the maximum indoor unit capacity of each room
When CTx = CTo, use the calculation formula below.
Room1: CTx × Corrected capacity for Room1/CTi
= 11.3 × (5.6 × 1.03)/13.3
= 4.9 kW
The capacity is enough for the cooling load of Room 1 (4.6 kW): A proper indoor unit is selected.
Room2: CTx × Corrected capacity for Room2/CTi
= 11.3 × (8.0 × 0.94)/13.3
= 6.4 kW
The capacity is enough for the cooling load of Room 2 (6.0 kW): A proper indoor unit is selected.
Note:
• If CTx = CTi, refer to the calculation formula in "Heating" to calculate the maximum indoor unit capacity of each
room.
• Go on to the selection of units for heating after the selection for cooling has successfully completed. If failed, try
again until proper units are selected.
OCH790 _14
Design condition
39ºC
10.6 kW
27ºC
20ºC
4.6 kW
24ºC
18ºC
6.0 kW
60 m
10
15
20
1.2
1.7
2.2
15
18
20
1.5
1.8
2.0
5.6 kW (Rated)
8.0 kW (Rated)
14.0 kW (Rated)
25
32
40
2.8
3.6
4.5
22
25
35
42
2.2
2.5
3.5
4.2
1.03 (Refer to Figure 1.)
Room 2 (18°C)
0.94 (Refer to Figure 1.)
0.92 (Refer to Figure 2.)
0.88 (Refer to "Correcting Capacity".)
50
63
71
80
100
5.6
7.1
8.0
9.0
11.2 14.0 16.0
50
60
71
80
100
5.0
6.0
7.1
8.0
10.0
125
140