4
SPECIFICATIONS
Model
Power source
Cooling capacity (Nominal)
Power input
Current input
COP
Temp. range of
Indoor
cooling
Outdoor
Heating capacity (Nominal)
Power input
Current input
COP
Temp. range of
Indoor
heating
Outdoor
Indoor unit
Total capacity
connectable
Model/ Quantity CITY MULTI
Sound pressure level (SPL)
(measured in anechoic room)
Sound power level (PWL)
(measured in anechoic room)
Refrigerant piping
Liquid pipe
diameter
Gas pipe
Fan
Type × Quantity
Airflow rate
Control, Driving mechanism
Motor output
External static press.
Compressor
Type × Quantity
Manufacturer
Starting method
Capacity control %
Motor output
Case heater
Lubricant
External finish
External dimension H × W × D
Protection
High pressure protection
devices
Inverter circuit (COMP./FAN)
Compressor
Fan motor
Refrigerant
Type × original charge
Control
Net weight
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Defrosting method
Standard
Document
attachment
Accessory
Optional parts
Remarks
*1.
Nominal cooling conditions:
Indoor:
Outdoor:
Pipe length:
Level difference:
*2.
Nominal heating conditions:
Indoor:
Outdoor:
Pipe length:
Level difference:
*3.
10 to 52°C D.B. [50 to 126°F D.B.], when connecting following models: PKFY-P10/15/20/25/32VLM, PFFY-P20/25/32VLEM, PFFY-P20/25/32VL-
RM(M), PFFY-P20/25/32VKM, PFFY-P20/25/32VCM; and M series, S series, and P series type indoor unit.
*4.
−15 to 52°C D.B. [50 to 126°F D.B.], when using an optional air protect guide [PAC-SH95AG-E]. However, this condition does not apply to the indoor
unit listed in *3.
*5.
When connecting 7 indoor units via branch box, connectable CITY MULTI indoor units are 3; connecting 8 indoor units via branch box, connectable
CITY MULTI indoor units are 2.
*6.
At least two indoor units must be connected when using branch box.
Notes:
• Nominal conditions *1, *2 are subject to ISO 15042.
• Due to continuing improvement, above specifications are subject to change without notice.
• See the following for unit conversion: kcal/h = kW × 860, Btu/h = kW × 3,412, cfm = m³/min × 35.31, lb = kg/0.4536
Above specification data is subject to rounding variation.
OCH790 _12
kW
*1
kcal/h
Btu/h
kW
A
kW/kW
W.B.
D.B.
kW
*2
kcal/h
Btu/h
kW
A
kW/kW
D.B.
W.B.
Branch box
*6
Mixed
Branch box
CITY MULTI
system
1 unit
*6
Branch box
Branch box
CITY MULTI
2 units
*6
Branch box
dB <A>
dB <A>
mm (in)
mm (in)
m³/min
L/s
cfm
kW
kW
kW
mm
in
kg (lb)
27°C D.B./19°C W.B. [81°F D.B/66°F W.B.]
35°C D.B. [95°F D.B.]
7.5 m [24-9/16 ft]
0 m [0 ft]
20°C D.B. [68°F D.B.]
7°C DB/6°C W.B. [45°F D.B./43°F W.B.]
7.5 m [24-9/16 ft]
0 m [0 ft]
PUMY-P112VKM6(-BS)
PUMY-P125VKM6(-BS)
PUMY-P112VKM6-ER(BS)
PUMY-P125VKM6-ER(BS)
1-phase 220-230-240 V, 50 Hz; 1-phase 220-230 V, 60 Hz
12.5
10,750
42,650
4.34
20.03 - 19.16 - 18.36,
23.08 - 22.08 - 21.16,
20.03 - 19.16
23.08 - 22.08
2.88
−5 to 52°C
14.0
12,040
47,768
3.49
16.11 - 15.41 - 14.77,
18.74 - 17.93 - 17.18,
16.11 - 15.41
18.74 - 17.93
4.01
−20 to 15°C
50 to 130% of outdoor unit capacity
P10 - P140 / 9
P10 - P140 / 10
P15 - P100 / 8
P15 - P100 / 8
P15 - P140 / 5
P15 - P140 / 5
P15 - P100 / 5
P15 - P100 / 5
P15 - P140 / 3 or 2
P15 - P140 / 3
*5
P15 - P100 / 7 or 8
P15 - P100 / 8
*5
49/51
69/71
15.88 (5/8)
Propeller Fan x 2
0.074 + 0.074
Scroll hermetic compressor x 1
Mitsubishi Electric Corporation
Cooling 26 to 100
Cooling 24 to 100
Heating 20 to 100
Heating 18 to 100
2.9
FV50S (2.3liter)
Galvanized Steel Sheet Munsell No. 3Y 7.8/1.1
1,338 × 1,050 × 330 (+40)
52-11/16 × 41-11/32 × 13 (+1-9/16)
High pressure switch
Overcurrent detection, Overheat detection (Heat sink thermistor)
Compressor thermistor, Overcurrent detection
Overheating, Voltage protection, Overcurrent detection
R410A 4.8 kg
Linear expansion valve
Cross Fin and Copper tube
Double pipe heat exchanger
Reversed refrigerant circuit
Installation Manual
Grounded lead wire ×1
Joint: CMY-Y62-G-E, Header: CMY-Y64/68-G-E, Branch box: PAC-MK34/54BC
PUMY-P140VKM6(-BS)
PUMY-P140VKM6-ER(BS)
14.0
15.5
12,040
13,330
47,768
52,886
5.00
5.17
23.86 - 22.83 - 21.87,
23.86 - 22.83
2.80
3.00
15 to 24°C
*3*4
16.0
18.0
13,760
15,480
54,592
61,416
4.06
4.63
21.37 - 20.44 - 19.59,
21.37 - 20.44
3.94
3.89
15 to 27°C
P10 - P140 / 12
P15 - P100 / 8
P15 - P140 / 5
P15 - P100 / 5
P15 - P140 / 3
P15 - P100 / 8
50/52
51/53
70/72
71/73
9.52 (3/8)
110
1,833
3,884
DC control
0
Inverter
Cooling 21 to 100
Heating 17 to 100
3.5
3.9
0
122 (269)