Mitsubishi Electric CITY MULTI PUMY-P112VKM6 Service Manual page 140

Advertisement

Touch the [Set] button to save the setting.
2. To search for an interlocked setting
• Touch the [Conf] button to display in the left column the addresses of the units that are interlocked with the unit
whose address was set in the Add. 1 section.
3. To delete the interlock settings
• After taking Step 2 above, select the address to be deleted in the Add. 2 section, and then touch the [Del] button.
Note:
• When the setting or deletion is successfully completed, "Completed" will appear below [Function] field on the screen.
If setting or deletion fails, "Request denied" will appear below [Function] field on the screen.
[Interlocked LOSSNAY]
00
1 IC
00
7 IC
Add. 1
00
00
2 IC
8 IC
Add. 2
00
3 IC
00
9 IC
00
4 IC
0
10 IC
Function
00
0
5 IC
11 IC
00
6 IC
0
12 IC
Back
■ Search connection information
Use this screen to specify a unit and search for the controllers that are connected to the unit.
1. Select an address in the [Address] field.
2. Touch the [Conf] button to search for the interlocked units.
The results will appear in the left column. (When multiple units are found, the addresses that do not fit on the first
page will appear on the successive pages.)
Search error: "Request denied." will appear.
[Search connection information]
00
1 IC
Address
00
2 IC
00
3 IC
00
4 IC
Function
00
5 IC
00
6 IC
Back
After completing the settings, touch the [Back] button on the setup screen. The message "Collecting the information
from the air conditioner." will appear, and then the screen will jump to the home screen. This signals the completion of the
setup process. Access the Service Menu from the home screen to make the settings for other items as necessary.
OCH790 _140
-
00
+
1
-
0
13
+
Set Conf
Del
-
+
0
51
Conf