1102 (U2): Compressor temperature trouble
Diagnosis of failure
Continued from the previous page.
Disconnect the thermistor wiring to check the
resistance.
Is the resistance detected?
Check the voltage(*) and appearance of the
outdoor multi controller circuit board.
Is the voltage normal value?
Is it free from any trace of overheating
or burning?
Disconnect the indoor LEV wiring and check the
resistance.
Is the resistance detected?
*For the voltage, refer to "How to check the components".
OCH790 _35
No
Yes
No
Yes
No
Yes
Replace the thermistor.
Replace the outdoor multi controller circuit
board.
Replace the indoor LEV.
Replace the indoor controller board.
Chart 2 of 2