Mitsubishi Electric CITY MULTI PUMY-P112VKM6 Service Manual page 101

Advertisement

SW1
Contents
setting
No. 12345678
24
00011000 Indoor unit
operation mode
25
10011000 Indoor unit
operation display
26
01011000 Capacity code
(No. 1 indoor unit)
27
11011000 Capacity code
(No. 2 indoor unit)
28
00111000 Capacity code
(No. 3 indoor unit)
29
10111000 Capacity code
(No. 4 indoor unit)
30
01111000 Capacity code
(No. 5 indoor unit)
31
11111000 IC1 operation
mode
32
00000100 IC2 operation
mode
33
10000100 IC3 operation
mode
34
01000100 IC4 operation
mode
35
11000100 IC5 operation
mode
36
00100100 OC operation
mode
37
10100100 External connec-
tion status
38
01100100 Communication
demand capacity
39
11100100 Number of
compressor ON/
OFF
40
00010100 Compressor
operating current
41
10010100 Input current of
outdoor unit
42
01010100 Thermo-ON
operating time
43
11010100 Total capacity of
thermo-ON
44
00110100 Number of indoor
units
45
10110100 DC bus voltage
46
01110100 State of LEV
control
47
11110100 State of compres-
sor frequency
control 1
48
00001100 State of compres-
sor frequency
control 2
49
10001100 Protection input
50
01001100 The second
current value
when micropro-
cessor of power
board abnormality
is detected
51
11001100 Heatsink tem-
perature when
microprocessor of
power board
abnormality is
detected
OCH790 _101
1
2
3
No.1 unit
No.2 unit
No.3 unit
mode
mode
mode
Cooling: light on, Heating: light blinking, Stop fan: light off
No.1 unit
No.2 unit
No.3 unit
Thermo ON
Thermo ON
Thermo ON
0–255
Notes:
•Display of indoor unit capacity code
•The No. 1 unit will start from the M-NET address with the lowest number
STOP
Fan
Cooling
thermo-ON
Note: Display of indoor unit operating mode
Compressor
Heating/
Abnormal/
ON/OFF
Cooling
normal
Note: Light on/light off
CN3N1–3
CN3N1–2
CN3S1–2
input
input
input
Note: Input: light off, No input: light on
0–255 (%)
Note: Display of communication demand capacity
0000–9999 (unit: x10)
Note: Display a count of compressor operation/stop
0–999.9 (Arms)
Note: Display detected current
0000–9999 (unit: x10)
Note: Display cumulative time of thermo-ON operation
0–255
Note: Display total capacity code of indoor units in thermo-ON
0–255
Note: Display number of connected indoor units
0–9999 (V)
Note: Display bus voltage
Td over heat
SHd de-
Min.Sj
prevention
crease
correction
prevention
depends on
Td
Note: Display active LEV control
Condensing
Compressor
temperature
temperature
limit control
control
Note: Display active compressor frequency control
Heat sink
Secondary
Input current
over heat
current
control
prevention
control
control
Note: Display active compressor frequency control
63LS
HIC abnor-
abnormality
mality
0–999.9[Arms]
Note: Display data at time of abnormality
−99.9–999.9 (°C)
Note: Display data at time of abnormality
LED1, 2
4
5
6
No.4 unit
No.5 unit
No.6 unit
mode
mode
mode
No.4 unit
No.5 unit
No.6 unit
Thermo ON
Thermo ON
Thermo ON
Cooling
Heating
Heating
thermo-OFF
thermo-ON
thermo-OFF
DEFROST/
Refrigerant
Excitation
NO
pull back/no
current/no
CN3D1-3
CN3D1-2
input
input
Min.Sj
LEV opening
LEV opening
correction
correction
correction
depends on
depends on
depends on
Shd
Pd
Td
Discharge
Pd abnormali-
Pd Back up
temp.
ty control
control
(heating)
(heating)
(heating)
backup
control
Frequency
Low pressure
restrain of
decrease
receipt
prevention
voltage
change
Frozen
4-way valve
Delay caused
protection
disconnection
by blocked
abnormality
valve in
cooling mode
7
8
No.7 unit
No.8 unit
mode
mode
No.7 unit
No.8 unit
Thermo ON
Thermo ON
3-min delay/
no
Correction of
high com-
pression ratio
prevention
Freeze
prevention
control at the
beginning of
SHd
Hz-up inhibit
control at the
beginning of
SHd
TH6 abnor-
Power
mality
module
abnormality