SW1
Contents
setting
No. 12345678
52
00101100 Outdoor LEV-A
opening pulse
53
10101100 Outdoor LEV-A
opening pulse
abnormality delay
54
01101100 Outdoor LEV-A
opening pulse
abnormality
55
11101100 Outdoor LEV-B
opening pulse
56
00011100 Outdoor LEV-B
opening pulse
abnormality delay
57
10011100 Outdoor LEV-B
opening pulse
abnormality
58
01011100 63LS (Low
pressure)
59
11011100 63LS abnormality
delay
60
00111100 63 LS abnormality
61
10111100 TH2 (HIC pipe)
62
01111100 TH2 (HIC)
abnormality delay
63
11111100 TH2 (HIC)
abnormality
64
00000010 Operational
frequency
65
10000010 Target frequency
66
01000010 Outdoor fan
control step
number
69
10100010 IC1 LEV Opening
pulse
70
01100010 IC2 LEV Opening
pulse
71
11100010 IC3 LEV Opening
pulse
72
00010010 IC4 LEV Opening
pulse
73
10010010 IC5 LEV Opening
pulse
74
01010010 High pressure
sensor (Pd)
75
11010010 TH4(Compressor)
(Td) data
76
00110010 TH6(Suction pipe)
(ET) data
77
10110010 TH7 (Ambient)
data
78
01110010 TH3 (Outdoor
liquid pipe) data
80
00001010 TH8 (Heat sink)
data
81
10001010 IC1 TH23 (Gas)
82
01001010 IC2 TH23 (Gas)
83
11001010 IC3 TH23 (Gas)
84
00101010 IC4 TH23 (Gas)
85
10101010 IC5 TH23 (Gas)
86
01101010 IC1 TH22 (Liquid)
87
11101010 IC2 TH22 (Liquid)
88
00011010 IC3 TH22 (Liquid)
89
10011010 IC4 TH22 (Liquid)
90
01011010 IC5 TH22 (Liquid)
91
11011010 IC1 TH21 (Intake)
92
00111010 IC2 TH21 (Intake)
93
10111010 IC3 TH21 (Intake)
94
01111010 IC4 TH21 (Intake)
95
11111010 IC5 TH21 (Intake)
96
00000110 Outdoor SC
(cooling)
97
10000110 Target subcool
step
98
01000110 IC1 SC/SH
99
11000110 IC2 SC/SH
100 00100110 IC3 SC/SH
101 10100110 IC4 SC/SH
102 01100110 IC5 SC/SH
103 11100110 Discharge
superheat (SHd)
105 10010110 Target Pd display
(heating) kgf/cm²
106 01010110 Target ET display
(cooling)
OCH790 _102
1
2
3
0–2000 (pulse)
Note: Display of opening pulse of outdoor LEV
−99.9–999.9 (kgf/cm²)
Note: Display of data from sensor and thermistor
−99.9–999.9 (°C)
Note: Display of data from sensor and thermistor
0–255 (Hz)
Note: Display of actual operating frequency
0–255 (Hz)
Note: Display of target frequency
0–15
Note: Display of number of outdoor fan control steps (target)
0–2000 (pulse)
Note: Display of opening pulse of indoor LEV
−99.9–999.9 (kgf/cm²)
Note: Display detected data of outdoor unit sensors and thermistors
−99.9–999.9 (°C)
Note: Display detected data of outdoor unit sensors and thermistors
−99.9–999.9 (°C)
(When indoor unit is not connected, it is displayed as 0.)
Note: Display detected data of indoor unit thermistors
−99.9–999.9 (°C)
Note: Display of outdoor subcool (SC) data
−2–4
Note: Display of target subcool step data
−99.9–999.9 (°C)
During heating: subcool (SC)
During cooling: superheat (SH) (Fixed to "0" during cooling operation)
Note: Display of indoor SC/SH data
−99.9–999.9 (°C)
Note: Display of outdoor discharge superheat (SHd) data
Pdm (0.0–30.0) (kgf/cm²)
Note: Display of all control target data
ETm (−2.0–23.0) (°C)
Note: Display of all control target data
LED1, 2