CPO-PC400-W/CPO-PC400-UW HVAC CONTROLLER

Connection to Buses

Table 12. Connection to Buses
Max. No. of
Protocols
Devices per
Channel
Panel Bus
16
CP-IO Bus
16
Field Bus
31
MSTP
30
Modbus
30
M-Bus**
60
C-Bus*
30
NOTES:
The communication rate across each commu-
nication interface is dependent upon the given
communication protocol.
*Not more than one channel can be configured
as C-Bus channel.
**Not more than one channel can be configured
as M-Bus channel.
**The CPO-PC400-W/CPO-PC400-UW con-
troller can function as an M-Bus Master. It uses
a standard level converter (e.g. PW60) to con-
nect to the M-Bus devices.
EN0B-0085 IE10 R0420
Yes
Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
No
Yes
Yes
Yes
No
Yes**
Yes**
Yes**
No
Yes*
Yes*
Yes*
No

Communication Baud Rates

Table 13. Communication Baud Rates
Ethernet
BACnet MSTP
Modbus
Panel Bus
CP-IO Bus
C-Bus
M-Bus
Field Bus
Wi-Fi
Bluetooth
MMI Port
The country code for the CPO-PC400-W is con-
figurable to comply with local country regula-
tions.

Connection to Panel Buses

The CPO-PC400-W/CPO-PC400-UW can communicate
with various Panel Bus I/O modules. See "Connection to
Panel Bus" section on pg. 18.
Table 14. Panel I/O modules
Name
XF821
XF822
XFR822
XF823
8
10/100 Mbit/s, RJ45
9.6, 19.2, 38.4, 76.8, 115.2 Kbps
0.3 to 115.2 Kbps
115.2 Kbps
56.7 Kbps
9.6, 38.4, and 76.8 Kbps
0.3 to 19.2 Kbps
38.4 Kbps
802.11b: up to 11 Mbps
802.11a/g: up to 54 Mbps
802.11n: up to 150 Mbps
802.11ac: up to 433 Mbps
BR: up to 1Mbps
EDR: up to 3Mbps
BLE: up to 1Mbps
5Vdc power output and RS485
Descripti
on
Pluggable
8
AI module
Pluggable
8
AO
module
Pluggable
8
AO
module
Pluggable
12
BI module
8
8
8
12