CPO-PC400-W/CPO-PC400-UW HVAC CONTROLLER
CONNECTION VIA RS485 INTERFACES 1, 2, OR 3
R
T
5V_ISO
GND_ISO
Isola on
Barrier
5V
GND
RX
TX
CPO-PC400-W/CPO-PC400-UW
Fig. 17. Connection (L > 3 m) of RS485 interfaces 1, 2, or 3 (RS485 interface 1 shown) to a Field Bus
NOTES:
Signal ground (signal reference) connection is recommended. For more information, see "General Information
on the RS485 Standard" section on page 7.
N = max. 31 unit loads.
The size of the transformer must always be calculated according to the power consumption of the connected
FBAs.
For communication cable lengths, transmission speeds, and termination, see "General Information on the
RS485 Standard" section on page 7. For fusing, see "Fusing" section on page 11.
EN0B-0085 IE10 R0420
110VAC/230VAC
24VAC
F1
26
L > 3m
FBA #1
Shielding
Op onal
A
F2
24VAC
110VAC / 230VAC
FBA #N
R
T
A+C = MAX.20 Meters
C