Basic Installation and Operation
Guide
MP.4 Metering (Metering Page 4)
Displays the present status of the soft start
*Screen 1: Displays the present state of the unit as follows:
Screen 2: D isplays the amount of time remaining before an overload trip will
occur.
Screen 3: Displays the amount of time remaining from a thermal inhibit. The inhibit
time comes from the amount of thermal register remaining versus the amount of
thermal capacity required to start.
Screen 4: Displays the coast down time remaining (Backspin time). The time
remaining depends upon the user setting in Setpoint Page 8, Coast Down Time.
Screen 5: Displays the amount of time remaining before a start command can be
given. The time remaining depends upon the setting in Setpoint page 5.
Screen 6: If the number of starts per hour has exceeded the setting in Setpoint
page 8.
* NOTE: Screen 1 CURRENT STATUS Screens include:
MOTOR STOPPED
READY TO START
MOTOR STARTING
MULT. OF FLA
MOTOR RUNNING
AT ###.## X FLA
LAST TRIP CAUSE
NONE (or trip cause)
PROGRAMMING
SETPOINTS
MOTOR STATUS
UNKNOWN STATE ###
TOSHIBA
(Displays relay state upon error)
JKSSS Series Solid State Soft Starters
METERING PAGE 4
STATUS
Screen 1
*(CURRENT STATUS)
Screen 2
O/L TIME LEFT TO TRIP
TRIP: ###### SEC
Screen 3
THERM INH TIME LEFT
: #### MIN
Screen 4
COAST DOWN TIMER
TIME LEFT: #:## MIN
Screen 5
TIME BETWEEN STARTS
TIME: #:## MIN
Screen 6
STARTS PER HOUR TIME
## ## ## ## ## ## ##
MENU
77