Sp.6 User I/O Configuration - Toshiba JKSSS Series Instruction Manual

Medium voltage solid state starter
Table of Contents

Advertisement

Basic Installation and Operation
Guide
SP.6 User I/O Configuration (Setpoint Page 6)
(Security Level 2)
(DOWN ARROW 5 TIMES)
MENU
User I/O Configuration
TACHOMETER SCALE
SELECTION: DISABLED
Option: Enabled or
Disabled
TACH ACCEL TRIP MODE
SELECT: DISABLED
Option: Underspeed,
Overspeed or Disabled
ANALOG OUTPUT #1
:RMS CURRENT
Range:
Analog Output Range
RPM 0 - 3600
Hottest Bearing 0 - 200°C
Hottest Stator RTD 0 - 200°C
RMS Current 0 - 6500A
% Motor Load 0 - 1000%
KW 0-30000 KW
OFF
Increments of 1
ANALOG OUTPUT #2
:% MOTOR LOAD
Range: See Analog Output#1
Increments of 1
USER PROGRAMMABLE
EXTERNAL INPUTS
TOSHIBA
Page 6
Continued on Pg. 56
JKSSS Series Solid State Soft Starters
ENABLED
MANUAL TACH SCALE
4.0 mA: 0 RPM
Range: 0-3600RPM
Increments of 5
MANUAL TACH SCALE
20.0 mA: 2000 RPM
Range: 0-3600RPM
Increments of 5
TACH RAMP TIME
: 20 SEC
Range: 1-120 SEC.,Disabled
Increments of 1
TACH UNDERSPEED TRIP
PT: 1650 RPM
Range: 0-3600RPM
Increments of 5
TACH OVERSPEED TRIP
PT: 1850 RPM
Range: 0-3600RPM
Increments of 5
TACH ACCEL TRIP
DELAY: 1 SEC
Range: 1-60 SEC.
Increments of 1
ANALOG OUTPUT #1
4mA: 0
Range: 0-65535
Increments of 1
ANALOG OUTPUT #2
4mA: 0
Range: 0-65535
Increments of 1
ANALOG OUTPUT #1
20mA: 250
Range: 0-65535
Increments of 1
ANALOG OUTPUT #2
20mA: 1000
Range: 0-65535
Increments of 1
56

Advertisement

Table of Contents
loading

Table of Contents