Toshiba JKSSS Series Instruction Manual page 82

Medium voltage solid state starter
Table of Contents

Advertisement

Basic Installation and Operation
Guide
User Calculated K or Assign: When the Setpoint is set to ON, the soft starter will calculate the k constant factor for
biasing the thermal register, or the user may choose to assign the k value.
SP12.4 Press Enter to CLR Thermal Register: Allows the level three password user to clear the thermal register for
emergency restarts.
MENU
(DOWN ARROW 11 TIMES)
PAGE 12
SYSTEM SETPOINTS
TOSHIBA
DEFAULT
DISPLAY SCREEN
ALARMS
THERMAL
REGISTER
SETUP
INFORMATION
PRESS ENTER TO
CLR THERMAL
REGISTER
JKSSS Series Solid State Soft Starters
METERING DATA
PAGE #: 1
Enter Metering Page (1 - 4)
Number for display
RTD FAILURE ALARM
ALARM: DISABLED
Option: Enabled or
Disabled
THERMAL REGISTER
ALARM: 90%
Range: Off, 40 - 95%
Increments of 1
COLD STALL TIME
: O/L CLASS
Range: O/L CLASS,
4 - 40 SEC
Increments of 1
HOT STALL TIME
: 1/2 O/L CLASS
Range: 1/2 O/L CLASS,
4 - 40 SEC
Increments of 1
STOPPED COOL DOWN
TIME: 30 MIN
Range: 10 - 300 MIN
Increments of 1
RUNNING COOL DOWN
TIME: 15 MIN
Range: 10 - 300 MIN
Increments of 1
RELAY MEASURED COOL
RATES: DISABLED
Option: Enabled or
Disabled
THERMAL REGISTER
MINIMUM: 15%
Range: 10 – 50% ,Off
Increments of 1
MOTOR DESIGN AMBIENT
TEMPERATURE: 40 C
Range: 10 - 90 C
Increments of 1
MOTOR DESIGN RUN
TEMPERATURE: 80% MAX
Range: 50 - 100% of Motor
Stator Max Temp.
Increments of 1%
MOTOR STATOR MAX
TEMPERATURE: INS CLS
Range: Insulation Class
10 - 240 C
Increments of 1
I/B INPUT TO THERMAL
REGISTER: ENABLED
Option: Enabled or
Disabled
USE CALCULATED K OR
ASSIGN: 7
Range: 1 - 50, ON
METERING DATA
SCREEN #: 1
Enter Metering Screen
Number for display
THERMAL ALARM
DELAY: 10 SEC.
Range: 1 - 20 SEC.
Increments of 1
69