Toshiba JKSSS Series Instruction Manual page 73

Medium voltage solid state starter
Table of Contents

Advertisement

Basic Installation and Operation
Guide
SP.7 Custom Acceleration Curve (Setpoint Page 7) - Continued
(Security Level 3)
(Continued from Prev. page)
CUSTOM
CURVE A
CUSTOM
CURVE B
TOSHIBA
CURVE A VOLTAGE
LEVEL 8: 100%
Range: 0 - 100%
Increments of 1
CURVE A RAMP
TIME 8: 2 SEC
Range: 1 - 60 SEC
Increments of 1
CURVE A CURRENT
LIMIT: 350% FLA
Range: 200 - 500%
Increments of 10
CURVE B VOLTAGE
LEVEL 1: 25%
Range: 0 - 100%
Increments of 1
CURVE B RAMP
TIME 1: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE B VOLTAGE
LEVEL 2: 30%
Range: 0 - 100%
Increments of 1
CURVE B RAMP
TIME 2: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE B VOLTAGE
LEVEL 3: 37%
Range: 0 - 100%
Increments of 1
CURVE B RAMP
TIME 3: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE B VOLTAGE
LEVEL 4: 45%
Range: 0 - 100%
Increments of 1
CURVE B RAMP
TIME 4: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE B VOLTAGE
LEVEL 5: 55%
Range: 0 - 100%
Increments of 1
CURVE B RAMP
TIME 5: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
JKSSS Series Solid State Soft Starters
CUSTOM
CURVE B
Cont.
CUSTOM
CURVE C
(Continued on next page)
CURVE B VOLTAGE
LEVEL 6: 67%
Range: 0 - 100%
Increments of 1
CURVE B RAMP
TIME 6: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE B VOLTAGE
LEVEL 7: 82%
Range: 0 - 100%
Increments of 1
CURVE B RAMP
TIME 7: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE B VOLTAGE
LEVEL 8: 100%
Range: 0 - 100%
Increments of 1
CURVE B CURRENT
LIMIT: 350% FLA
Range: 200 - 500%
Increments of 10
CURVE C VOLTAGE
LEVEL 1: 25%
Range: 0 - 100%
Increments of 1
CURVE C RAMP
TIME 1: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE C VOLTAGE
LEVEL 2: 30%
Range: 0 - 100%
Increments of 1
CURVE C RAMP
TIME 2: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE C VOLTAGE
LEVEL 3: 37%
Range: 0 - 100%
Increments of 1
CURVE C RAMP
TIME 3: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
60