Chapter 5 - Setpoint Programming
The soft starter has thirteen programmable setpoint pages which define the motor data, ramp curves, protection, I/O
configuration and communications. In Section 5.1, the setpoint pages are outlined in chart form. In Section 5.2 the
setpoint pages are illustrated and defined for easy navigation and programming. Note: setpoints can only be changed
when the starter is in the Ready Mode. The soft start will not start when it is in programming mode.
5.1 Setpoints Page List
These charts list the Setpoint Page, the programmable functions and the section.
5.1.1 Basic Configuration (Setpoint Page 1)
Setpoint
Security
Page
Level
Motor Full Load Amps (FLA)
Service Factor
Overload Class
NEMA Design
Insulation Class
Line Voltage
Line Frequency
5.1.2 Starter Configuration (Setpoint Page 2)
Setpoint
Security
Page
Level
Start Control Mode
Jog Voltage
Start Ramp #1 Type
Initial Voltage #1
Ramp Time #1
Current Limit #1
Initial Current #1
Ramp Time #1
Maximum Current #1
Start Ramp #2 Type
Initial Voltage #2
Ramp Time #2
Current Limit #2
Initial Power #2
Ramp Time #2
Maximum Power #2
Kick Start Type
Kick Start Voltage
Kick Start Time
Deceleration
Start Deceleration Voltage
Stop Deceleration Voltage
Deceleration Time
Timed Output Time
Run Delay Time
At-Speed Delay Time
Bypass Pull-in Current
TOSHIBA
Description
Model dependent
1.15
10
B
B
Model dependent
60
Description
Start Ramp 1
50%
Voltage
20%
10 sec
350% FLA
200% FLA
10 sec
350% FLA
Disabled
60%
10 sec
350% FLA
20%
10 sec
80%
Disabled
65%
0.50 sec
Disabled
60%
30%
5 sec
Off
1 Sec
1 Sec
100% FLA
JKSSS Series Solid State Soft Starters
Factory Setting
Default
50 - 100% of Unit Max Current Rating
(Model and Service Factor dependent)
1.00 – 1.3
O/L Class 5-30
A-F
A, B, C, E, F, H, K, N, S
1000 to 7200V
50 or 60 HZ
Factory Setting
Default
Jog, Start Ramp 1, Start Ramp 2, Custom
Accel Curve, Start Disabled, Dual Ramp,
Tach Ramp
5-75%, Off
Voltage, Current
0-100%
1-120 sec
200-500 %
0-300 %
1-120 sec
200-500 %
Disabled, Voltage, Power
0-100 %
1-120 sec
200-500 %
0-100 %
1-120 sec
0 – 300 %
Voltage or Disabled
10-100 %
0.10-2.00
Enabled or Disabled
0-100 %
0-59 %
1-60 sec
1-1000 sec, Off
1-30 sec, Off
1-30 sec, Off
90 – 300%
Range
Section
Range
Section
SP1.1
SP1.2
SP1.3
SP1.4
SP1.5
SP1.6
SP1.7
SP2.1
SP2.2
SP2.3
SP2.4
SP2.5
SP2.6
SP2.7
SP2.8
SP2.9
SP2.10
37