Trane TVR Pro CO Series Service Manual page 94

Hide thumbs Also See for TVR Pro CO Series:
Table of Contents

Advertisement

2.17 P1: Discharge pipe high pressure protection
Digital display output
Description
 All units stop running.
 Error code is only displayed on the unit with the error.
Trigger / recover condition
 Trigger condition: Discharge pressure ≥ 4.3MPa.
 Recover condition: Discharge pressure ≤ 4.0MPa for 2 minutes.
 Reset method: Resume automatically.
Possible causes
 Outdoor unit stop valves are closed.
 High pressure sensor not connected properly or has malfunctioned.
 Excess refrigerant.
 System contains air or nitrogen.
 High pressure side blockage.
 Poor condenser heat exchange.
 Main PCB damaged.
Procedure
ODU stop valves are closed
High pressure sensor connection on main
High pressure sensor has failed
P1
No
PCB is loose
1
No
2
No
Yes
Open the stop valves
Yes
Ensure the sensor is connected properly
Yes
Replace the sensor
93
Flowchart continued on next page ...