2.5 E5: Abnormal power supply voltage
Digital display output
Description
 Abnormal power supply voltage.
 All units stop running.
 Error code is only displayed on the unit with the error.
Trigger / recover condition
 Trigger condition: Outdoor unit power supply phase voltage < 165V.
 Recover condition: Outdoor unit power supply phase voltage is > 180V.
 Reset method: Resume automatically.
Possible causes
 Outdoor unit power supply voltage is abnormal or a phase is missing.
 Loosened wiring within electric control box.
 High voltage circuit error.
 Main PCB damaged.