Trane TVR Pro CO Series Service Manual page 66

Hide thumbs Also See for TVR Pro CO Series:
Table of Contents

Advertisement

2.6 E7: Temperature sensor (T7C1/2) error
Digital display output
Description
 A compressor top temperature sensor or discharge pipe temperature sensor (T7C1/2) error.
 All units stop running.
 Error code is only displayed on the unit with the error.
Trigger / recover condition
 Trigger condition: Discharge pressure ≥ 3MPa and discharge temperature < 15
 Recover condition: Discharge pressure and temperature go back to normal.
 Reset method: Manually restart.
Possible causes
 Temperature sensor not connected properly or has malfunctioned.
 Damaged main PCB.
o
C for 2 minutes.
65

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents