Table 5-2.1: Main PCB ports
Label
Port code
1
CN18
2
CN19
3
CN4
4
CN5
5
CN3
6
CN13
7
CN17
8
CN15
9
CN16
10
CN8
11
CN1
12
CN6
13
CN22-CN23
14
CN26
15
CN27
16
CN9
17
CN28
18
CN71
19
CN70
20
CN72
21
CN82
CN41, CN43,
22
CN46
23
CN30
24
CN66-CN67
Content
Reserved
Low pressure switch connection
Compressor top temperature sensor (single compressor
units) or compressor A compressor top temperature sensor
(dual compressor units) connection
Discharge pipe temperature sensor (single compressor units)
or compressor B compressor top temperature sensor (dual
compressor units) connection
Inverter module temperature sensor A connection
Inverter module temperature sensor B connection
High pressure sensor connection
Reserved
Reserved
Reserved
Outdoor ambient temperature sensor and outdoor heat
exchanger temperature sensor connections
Reserved
Communication port to outdoor units
Communication port to compressor drive board
Communication port to fan drive board
Communication USB port
Reserved
Reserved
EXVA drive port
Reserved
Control port of relay for AC filter board
Solenoid valve drive ports
Power input of main board
Power supply to compressor crankcase heater
/
0V or 5V DC
0-5V DC (varying)
0-5V DC (varying)
0-5V DC (varying)
0-5V DC (varying)
0-5V DC (varying)
/
/
/
0-5V DC (varying)
/
2.5-2.7V DC
2.5-2.7V DC
2.5-2.7V DC
2.5-2.7V DC
/
/
0V or 12V DC
/
0V or 12V DC
0V or 220V AC
220V AC between A/B/C and N;
380V AC between A,B and C
220V AC
43
Port voltage

Hide quick links: