Trane TVR Pro CO Series Service Manual page 47

Hide thumbs Also See for TVR Pro CO Series:
Table of Contents

Advertisement

Menu mode function:
Table 5-2.3: Menu mode function
Digital display
content
n14
Debug mode
n16
Maintenance mode
n24
Reserved
n25
Reserved
n26
Backup run
n27
Vacuum mode
n31
History error codes
n32
Cleaning history error codes
n33
Reserved
n34
Factory reset
n41
Power limitation mode 1
n42
Power limitation mode 2
n43
Power limitation mode 3
n44
Power limitation mode 4
n45
Power limitation mode 5
n46
Power limitation mode 6
n47
Power limitation mode 7
nb1
Fahrenheit degree setting (
nb2
Celsius degree setting (
nb3
Exit auto power save mode
nb4
Enter auto power save mode
nb5
Auto snow-blowing mode 1 (customized)
nb6
Auto snow-blowing mode 2 (customized)
nb7
Exit auto snow-blowing mode
nb8
VIP address setting
nF1
Reserved
nF2
Reserved
Notes:
1. Auto power save mode means EMS mode, the evaporating temperature (in cooling) and condensing temperature (in heating) are automatically adjusted
according to both indoor and outdoor temperature to maximize the comfort and energy efficiency. Exit auto power save mode, the evaporating temperature
(in cooling) and condensing temperature (in heating) are fixed.
Menu mode
F)
o
C)
o
1
1
Only available for the master unit (all indoor units running in cooling mode)
Only available for the master unit, the system does not check the indoor units' number.
Only available for outdoor unit with two compressors. If one of the two compressors is
fail, the other compressor will keep running for up to 4 days and then stop automatically.
It is only used in maintenance process. The digital display displays "R006", all solenoid
valves are open and EXVs are open to the maximum steps.
Display recent ten history error codes
Only available for the master unit
Only available for the master unit, 100% capacity output
Only available for the master unit, 90% capacity output
Only available for the master unit, 80% capacity output
Only available for the master unit, 70% capacity output
Only available for the master unit, 60% capacity output
Only available for the master unit, 50% capacity output
Only available for the master unit, 40% capacity output
Only available for the master unit
Only available for the master unit
Only available for the master unit
Only available for the master unit
According to outdoor ambient temperature (T4), the outdoor fan(s) periodically stop for
15 minutes and run for 2 minute
According to outdoor ambient temperature (T4), the outdoor fan(s) periodically stop for
30 minutes and run for 2 minute
The digital display will display "IdXX", "XX" stands for VIP address, use UP / DOWN button
to change the VIP address and press OK button to confirm the specified VIP address.