Trane TVR Pro CO Series Service Manual page 36

Hide thumbs Also See for TVR Pro CO Series:
Table of Contents

Advertisement

1 Outdoor Unit Field Settings
1.1 PCB Switches and Switch Settings
Figure 4-1.1: Outdoor unit main PCB switches
Table 4-1.1: Outdoor unit main PCB switch settings
Switch
Setting
S5
Reserved
Reserved
S6-1
Clear indoor
unit addresses
S6-2
Addressing
S6-3
mode
Reserved
S8-1
Start-up time
S8-2
Reserved
S8-3
S7
Reserved
Controller type
S13
Outdoor unit
address
ENC1
Outdoor unit
capacity
ENC2
Network
address
ENC4
Switch positions
1
2
Reserved
No action (default)
Clear indoor unit addresses
Auto addressing (default)
Manual addressing
Reserved
Start-up time is 12 minutes (default)
Start-up time is 7 minutes
Reserved
Use the new centralized controller (default)
Use the old centralized controller
Only 0, 1, 2 should be selected (default is 0)
0 is for master unit; 1 and 2 are for slave units
Only 0, 1, 2, 3, 4, 5, 6, 7, 8, 9, A, B should be selected
0: 8HP; 1: 10HP; 2: 12HP; 3: 14HP; 4: 16HP; 5: 18HP; 6: 20HP; 7: 22HP; 8: 24HP;
9: 26HP; A: 28HP; B:30HP
Only 0, 1, 2, 3, 4, 5, 6, 7 should be selected (default is 0)
35
Description
Table continued on next page ...