... flowchart continued from previous page
The fan motor is blocked or has failed
The power supply is abnormal
Voltage between P and N on fan module
Replacing the fan module resolves the
Replace outdoor main PCB
Notes:
1.
The normal voltage between P and N on the fan module is 540V DC.
No
No
is abnormal
1
No
error
No
Figure: Fan module P N terminals
Remove obstruction or replace the fan
Yes
Yes
Check the power supply equipment
Yes
Replace AC filter board