Trane TVR Pro CO Series Service Manual page 32

Hide thumbs Also See for TVR Pro CO Series:
Table of Contents

Advertisement

high temperatures. It is performed for each compressor and inverter module.
Figure 3-5.5: Inverter module temperature protection control
T
> 74
o
f
Compressor output reduced
T
> 79
o
f
Inverter module temperature protection,
Notes:
1.
T
: Heat sink temperature
f
Figure 3-5.4: Compressor current protection control
Current ≥ Current
Compressor current protection, error code xH4(xL0) is displayed
Compressor model
Normal operation
C
T
< 71
o
C
f
C
error code PL is displayed
Normal operation
Current < Current
max
LNB53
Current
48.5
max
T
< 65
C
o
f
When PL protection occurs 3 times
in 100 minutes, the C7 error is
displayed. When a C7 error occurs, a
manual system restart is required
before the system can resume
operation.
31
max
LNB65
59

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents