1.2.1.2 Silent mode setting
In silent mode 1 / 2 / 3 and night silent mode, the outdoor fan speed decreases gradually. In super silent mode 1 / 2 / 3 / 4,
not only the fan speed decreases gradually, but also the compressor frequency decreases gradually.
Table 4-1.3: Silent mode setting
Switch
ENC5
1.2.1.3 Maximum fan speed and capacity output control in different silent mode
Table 4-1.4: Maximum fan speed and capacity output control in different silent mode
ENC5
Switch
Description
positions
0
Night silent time is 6h/10h (default)
1
Night silent time is 6h/12h
2
Night silent time is 8h/10h
3
Night silent time is 8h/12h
4
No silent mode
5
Silent mode 1
6
Silent mode 2
7
Silent mode 3
8
Super silent mode 1
9
Super silent mode 2
A
Super silent mode 3
B
Super silent mode 4
Notes:
1.
Fan speed (rpm) for different fan speed index refers to Table 3-4.2 in Part 3, 4.6 "Outdoor Fan Control".
2.
If the system pressure is over 3.5MPa, the system exits silent mode automatically.
Switch positions
5
Silent mode 1 (only limit max. fan speed)
6
Silent mode 2 (only limit max. fan speed)
7
Silent mode 3 (only limit max. fan speed)
8
Super silent mode 1 (limit max. fan speed and compressor frequency)
9
Super silent mode 2 (limit max. fan speed and compressor frequency)
A
Super silent mode 3 (limit max. fan speed and compressor frequency)
B
Super silent mode 4 (limit max. fan speed and compressor frequency)
8-10HP
28
29
28
26
24
28
27
26
25
Description
Max. fan speed index
12HP
14-16HP
18HP
28
30
29
30
33
33
28
30
31
26
28
29
24
27
27
28
29
23
27
28
22
26
27
21
25
26
20
38
1
20-22HP
24-26HP
28-30HP
29
31
31
35
33
35
31
31
31
29
29
29
27
27
27
23
28
28
22
27
27
21
26
26
20
25
25
Max.
capacity
output
8-30HP
100%
80%
70%
60%
50%