Instruction Manual
Technical Data
1.4
Device version
Data
Communication
Device class
Device profile
Device model
Connections
Device address
Power supply
Permissible bus voltage
Current consumption of bus
Digital output 1
Digital output 2
Explosion protection
Order Data
1.5
The former order procedure is still valid with the following deviations:
· For the PROFIBUS PA version the "0" must be replaced by a "1" at the 13
number.
· For the explosion protection, version II 2G EEx dem[ia] IIC T6 is available in place of version II 2G
EEx dem[ib] IIC T6, order code "G".
4 to 20 mA/HART
PROFIBUS PA
Explosion protection
D Without explosion protection
D With explosion protection:
-- II 2G EEx d IIC T6 (not for PG 13.5)
-- II 2G EEx dem IIC T6
-- II 2G EEx dem [ib] IIC T6 (only for 4--20 mA/HART,
not for 120--230 V, only passive pulse output)
-- II 2G EEx dem [ia] IIC T6 (only for PROFIBUS PA,
not for 120--230 V)
8
Order number 7ME30xx-xxxxx-1xxx (Software version 2.00 onward)
According to operating manual of the 20 mA/HART version
(order number C79000-B5600-C110) with the following deviations:
Layer 1+2 acc. to PROFIBUS PA, transmission technique acc. to
IEC 61158-2; Slave function
Layer 7 (protocol layer) according to PROFIBUS DP, Standard
EN 50 170 incl. DPV1
B
3.0
Modular function device
Up to 4 simultaneous C2 connections (Master class 2) are supported;
Automatic disconnection approx. 60 s after communication abort
126 in the as-delivered state
Separate power supply for basic unit
9 to 32 V; for devices in ignition protection type II 2G EEx dem[ia]
IIC T6 see table of the EC Type Examination Certificate
10 mA
in case of error ≤14.5 mA (electronic current limiter)
Only passive signals
Omitted
II 2G EEx d IIC T6
II 2G EEx dem IIC T6
II 2G EEx dem[ia] IIC T6
See EC Type Examination Certificate for permissible maximum values
of voltage, current, power, inductance and capacitance
(see chapter 7)
th
7ME30xx --
--
jjjjj
data position in the order
jjjj
0
1
A
C
D
F
G
SITRANS F with PROFIBUS PA
C79000-B5676-C114-03