Electrode Position; Combustion Head Adjustment; Fan Gate Adjustment - Riello PRESS GV INCINERATOR Installation, Use And Maintenance Instructions

Oil burner
Table of Contents

Advertisement

5.8

Electrode position

Make sure that the electrodes are positioned as
shown in Fig. 13.
WARNING
5.9

Combustion head adjustment

The setting of the combustion head depends exclusively on the
delivery of the burner - in other words, the combined delivery of
the two nozzles selected on page 14.
Set the screw 1)(Fig. 15) in such way that its rear surface corre-
sponds to the notch number shown in diagram (Fig. 14).
Example:
The burner with two 5.00 GPH nozzles and 12 bar pump pres-
sure.
Find the delivery of the 5.00 GPH nozzle in Tab. I on page 15 =
21.2 kg/h.
Diagram (Fig. 14) indicates that for a delivery of 21.2 kg/h the
burner requires the combustion head to be set to approx.
3.1 notches, as shown in Fig. 16.
8
7
6
5
4
3
2
1
0
15
20
Light oil delivery - kg/h
5.10

Fan gate adjustment

The fan gate is set using the indexed selector 1)(Fig. 17), after
having loosened the nut 2).
This setting must be adapted case by case to the burner's deliv-
ery and combustion chamber pressure.
The first time the burner is fired, this setting should be left as orig-
inally set by the manufacturer: notch 2.
20098582
Installation
S9273
25
30
Fig. 14
16
GB
D408
D2560
D336
D412
Fig. 13
Fig. 15
Fig. 16
Fig. 17