This section shows examples of wiring of parts such as an emergency stop switch and start/stop/reset switch.
Double wiring (using test pulse outputs)
With two input modules with diagnostic functions, an emergency stop switch is wired as follows:
(1)
(1)
(1) Connect an emergency stop switch that has two normally closed contacts based on direct opening action, between X00 to X0F (input) terminals and T0 and
T1 (test pulse output) terminals.
■Input double wiring
Apply input double wiring in either of the following combinations.
• For the RX40NC6B (Main) and the RX40NC6B (Sub), wire even-numbered input terminals with T0 test pulse output
terminals.
• For the RX40NC6B (Main) and the RX40NC6B (Sub), wire odd-numbered input terminals with T1 test pulse output