Number of input ON times alarm detection count setting
Set the number of input ON times alarm detection count for each input.
■Buffer memory address
The following table shows the buffer memory address of this area.
Buffer memory name
X00
Number of input ON times
1208
alarm detection count setting
1209
■Setting range
• The available range is 1 to 4294967295.
• The number of input ON times alarm detection count setting error (error code: 196H) occurs in the input terminal where a
value out of the setting range has been set.  indicates the number of an I/O terminal in which the error has occurred. ( =
0H to FH)
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y12) to enable the setting.
■Default value
The default value is set to 1 for all the inputs.
Event time stamp function enable/disable
Set whether to enable or disable the event time stamp function for each input.
b15
b14
b13
b12
b11
b10
X0F
X0E
X0D
X0C
X0B
X0A
(1) 0: Disable, 1: Enable
■Buffer memory address
The following table shows the buffer memory address of this area.
Buffer memory name
Event time stamp function enable/disable
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y12) to enable the setting.
■Default value
The default value is set to 0 (Disable) for all the inputs.
X01
X02
X03
X04
X05
1210
1212
1214
1216
1218
1211
1213
1215
1217
1219
b9
b8
b7
b6
b5
b4
X09
X08
X07
X06
X05
X04
X0 to XF
1248
X06
X07
X08
X09
1220
1222
1224
1226
1221
1223
1225
1227
b3
b2
b1
b0
(1)
X03
X02
X01
X00
X0A
X0B
X0C
X0D
X0E
1228
1230
1232
1234
1236
1229
1231
1233
1235
1237
APPX
Appendix 3 Buffer Memory
X0F
1238
1239
A
99

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-ry40pt5b

Table of Contents