Installation
May 2020
8. Install the bolts in a cross pattern and hand-tighten.
9. Using a torque wrench on the bolt, tighten the assembly in a cross-pattern to
3.11
FUW flush flanged groove type seals
Figure 3-14: FUW Flush Flanged Type Seal—EN1092-1 Type D
A. Process flange
B. Diaphragm
C. Connection to transmitter
3.11.1
Parts required for installation
The parts required to install the FUW flush flanged groove type seal will be defined here.
Prior to installation, you will need the following:
•
Torque wrench
•
Mounting hardware (end-user-supplied)
•
Gasket (end-user-supplied)
Verify the gasket material is appropriate for the application.
Inspect bolts to ensure the material is compatible with industry standards per the
application such as ASME PCC-1.
42
WARNING
Failure to properly install the gasket may cause process leaks, which can result in
death or serious injury.
ensure even installation
3-3
based on size and bolt material. Consider leak checking the installation to
ensure a robust connection.
(Torque
sequence). The bolts should be torqued per
Reference Manual
00809-0100-4002
Table
C
B
Rosemount DP Level