(2) 321 to 322 Measurement setting
Set the dead band of measurement display, and with or without of tidal current measurement.
321
Dead band of measurement
◆ 321 Measurement dead band
Set the dead band of measurement display.
By this setting, variation of less than this set value is
disregarded by voltage, current, active power, and reactive
power measurement display.
Setting range:0.0 to 2.0% (0.1% step)
Selection by + and - , set value is updated by SET .
Default setting:0.0% (None)
◆ 322 Tidal current measurement
By measurement of reactive power and a power factor,
0 (general measurement) or 1 (tidal current measurement
which was conscious of power transmission / power
receiving) can be selected.
Selection by + and - , set value is updated by SET .
Default setting:0 (General measurement)
General
0:
measurement
General measurement:Displays the polarity (LAG / LEAD) supplied from the power system side.
Tidal current measurement:Displays the polarity (LAG / LEAD) supplied from the power system side.
Image of reactive power and power factor display
Current
Power
CT
direction
receiving
Current
Power
CT
direction
transmission
<Note> When used in a place where power transmission operation is performed (supply from the power generation side
to the power system side), the polarity (LEAD / LAG) of reactive power and power factor measurement during
power transmission changes depending on the power flow measurement setting.
However, the meter display is LEAD on the left and LAG on the right.
RESET/
Tidal current measurement
SHIFT
RESET/SHIFT
Tidal current
1:
measurement
(Both power receiving and power transmission)
(At power receiving)
Displays the polarity (LAG / LEAD) supplied from the power generation side.
(At power transmission)
General measurement
Power receiving (Power purchase)
Voltage standard
Current of
Multimeter
leading phase
LEAD
LAG
270°
Reactive
power
LEAD
Multimeter
LEAD
LEAD
LAG
Reactive
180°
power
Power transmission
(Power selling)
Polarity as seen from the power receiving
side during power transmission (-W)
322
New setting
Current setting
Setting No.
Setting factor
New setting
Current setting
Setting No.
Tidal current measurement
Power receiving (Power purchase)
Current of
laging phase
Polarity
LAG
supplied
90°
from the
LAG
power
system side
Current of
laging phase
Polarity seen from the power transmission
side during power transmission (-W)
58
Dead band of measurement
Tidal current measurement
Voltage standard
Current of
Current of
laging phase
leading phase
LEAD
LAG
90°
270°
LAG
LEAD
180°
Current of
leading phase
Power transmission
(Power selling)
SQLC-220-086
Polarity
supplied from
the power
system side
Polarity
supplied from
the power
generation side