Daiichi Electronics SQLC-110L Instruction Manual page 42

Power line super multimeter
Hide thumbs Also See for SQLC-110L:
Table of Contents

Advertisement

(2) 121AL to 128AL Alarm output setting 【with an alarm output option】
Various setting and an output test are performed about an alarm output.
In case contact outputs 1 and 2 are alarm output specifications, the corresponding alarm output is setting.
121AL
Alarm 1 factor
RESET/
SHIFT
128AL
Alarm 2 test
◆ 121AL Alarm 1 factor setting,125AL Alarm 2 factor setting.
Set the output factor of alarms 1 and 2. Selection by + and - , set value is updated by SET .
Default value :1(DA:Demand current )
OFF:Nothing
9:Voltage
◆ 122AL Alarm 1 reset method setting,
126AL Alarm 2 reset method setting
Output action at the case of a reset of alarms 1 and 2 can be selected
from AUTO (automatic reset) and HOLD (manual reset).
In "AUTO (automatic reset)", an alarm output also constitutes OFF
according to a reset of an alarm. In "HOLD (manual reset)", even after
an alarm reset, an output holds ON.
The reset in this case (output OFF) is performed in RESET/SHIFT .
Selection by + and - , set value is updated by SET .
Default setting:AUTO (automatic reset)
◆ 123AL Alarm 1 contact delay time, 127AL Alarm 2 contact delay time
Set the contact delay time of alarms 1 and 2. The setting range is 0 to 300 seconds (1 second step).
Selection by + and - , set value is updated by SET .
Default setting:0 second (With no contact delay)
◆ 124AL Alarm 1 test, 128AL Alarm 2 test
The output of alarms 1 and 2 is tested. While pushing SET , an output is ON, and if it detaches, an output
switches OFF. In addition, about a reset of an alarm, it becomes action united with reset method setting
(automatic reset / manual reset) of each alarm output.
Setting No.
(Output OFF)
122AL
RESET/
Alarm 1
SHIFT
return method
127AL
RESET/
Alarm 2 contact
SHIFT
delay time
1:Demand
2:Demand
power
current
8:Harmonic
nth content
(Voltage)
Status of output
SET
Alarm 1 test
123AL
RESET/
Alarm 1 contact
SHIFT
delay time
126AL
RESET/
Alarm 2
SHIFT
return method
3:Distortion
factor
(Current)
7:Harmonic 5th
conversion content
(Voltage)
New setting
Setting No.
Status of output
(Output ON)
41
RESET/
124AL
SHIFT
Alarm 1 test
RESET/
125AL
SHIFT
Alarm 2 factor
4:Harmonic 5th
conversion content
(Current)
5:Harmonic
6:Distortion
factor
(Voltage)
Current setting
Setting №
SQLC-220-086
RESET/
SHIFT
nth content
(Current)