Daiichi Electronics SQLC-110L Instruction Manual page 44

Power line super multimeter
Hide thumbs Also See for SQLC-110L:
Table of Contents

Advertisement

◆ 136 Power factor operation method
The operation method of power factor measurement can be selected from
0 (instantaneous measurement) and 1 (averaging operator in a demand
time interval).
In case it is set as "1 (averaging operator in a demand time interval)",
power factor measurement is calculated from the operation method of a
power demand time interval and a demand active power meter.
Selection by + and - , set value is updated by SET .
Default setting:0 (Instantaneous measurement )
0:Instantaneous
measurement
(4) 141H to 14A Harmonic detection setting
Set the high-alarm value of each harmonic (current, voltage) measurement factor, factor,
5th conversion detection characteristics, and average time interval is performed.
141H
Current distortion
factor
upper limit
RESET/
SHIFT
◆ 141H Current distortion factor upper limit,
145H Voltage distortion factor upper limit.
Set the high-alarm value of distortion factor (current, voltage).
Setting range. Current:5 to 100% (1% step)
Voltage:1.0 to 20.0% (0.1% step)
Selection by + and - , set value is updated by SET .
Default setting:OFF [Non use] (Current, Voltage)
◆ 142H Current 5th conversion content upper limit,
146H Voltage 5th conversion content upper limit.
Set the high-alarm value of 5th conversion content
(current, voltage).
Setting range. Current:5 to 100% (1% step)
Voltage:1.0 to 20.0% (0.1% step)
Selection by + and - , set value is updated by SET .
Default setting:OFF [Non use] (Current, Voltage)
◆ 143 Current nth content factor,
147 Voltage nth content factor.
Set the factor (order) of nth content (current, voltage).
An order can be selected from n= 3, 4, 5, 7, 9, 11, 13, 15.
Selection by + and - , set value is updated by SET .
Default setting:5th (Current, Voltage)
◆ 144H Current nth content upper limit,
148H Voltage nth content upper limit.
Set the high-alarm value of nth content (current, voltage).
Setting range. Current:5 to 100% (1% step)
Voltage:1.0 to 20.0% (0.1% step)
Selection by + and - , set value is updated by SET .
Default setting:OFF [Non use] (Current, Voltage)
Averaging operator
1:
in a demand time
interval
142H
RESET/
Current 5th
SHIFT
conversion content
upper limit
147
Voltage nth
content factor
RESET/
SHIFT
148H
Voltage nth
content
upper limit
New setting
Setting No.
143
RESET/
Current nth
SHIFT
content factor
146H
Voltage 5th
RESET/
conversion content
SHIFT
upper limit
149
RESET/
5th conversion
SHIFT
detection
characteristics
Current distortion factor upper limit
43
Current setting
Power factor operation method
144H
RESET/
Current nth
SHIFT
content
upper limit
145H
Voltage distortion
RESET/
factor
SHIFT
upper limit
14A
RESET/
Average time
SHIFT
interval
Setting factor
New setting
Setting No.
Current setting
Setting factor
New setting
Setting No.
Current setting
Voltage nth content factor
SQLC-220-086
RESET/
SHIFT