ADAPT Parasol b
Technical description
Regulator's Modbus connections
RS 485
RS 485
MB 1
MB 2
SuperWISE bus
Sensor module
BMS bus
Pressure sensor
Slave controller
4x RS485, modular RJ12 6/6
22 & 23 parallel, master circuit
24 & 25 parallel, slave circuit
18
Swegon reserves the right to alter specifications.
The master circuit (22, 23) is used for communication
between ADAPT Parasol master units and communication
from the master unit up to the superordinate system, for
example, SuperWISE.
The slave circuit (24, 25) is used for communication
between slave units ADAPT Parasol and to connect the
sensor module, pressure sensor, VOC sensor, etc.
Note that 22 and 23 are parallel (same function), and 24
and 25 are parallel. Important to distinguish between the
pairs 22/23 and 24/25.
The order of the connected units on each circuit is not
important, however it is more important to avoid so-
called Stubs and build just one circuit instead.
25/11/2014
www.swegon.com