Emerson Rosemount 3051 Series Quick Start Manual page 35

Pressure transmitter and flow meters with 4-20 ma hart revision 5 and 7 protocol
Hide thumbs Also See for Rosemount 3051 Series:

Advertisement

January 2020
4.6
Brazil
4.6.1
E2 INMETRO Flameproof
Certificate UL-BR 13.0643X
Standards ABNT NBR IEC 60079-0:2013; ABNT NBR IEC 60079-1:2016;
Markings
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm with less than 1 mm
thickness that forms a boundary between zone 0 (process
connection) and zone 1 (all other parts of the equipment). The model
code and datasheet are to be consulted for details of the diaphragm
material. Installation, maintenance, and use shall take into account
the environmental conditions to which the diaphragm will be
subjected. The manufacturer's instructions for installation and
maintenance shall be followed in detail to assure safety during its
expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic
discharge. Avoid installations that could cause electrostatic build-up
on painted surfaces and only clean the painted surfaces with a damp
cloth. If paint is ordered through a special option code, contact the
manufacturer for more information.
4.6.2
I2 INMETRO Intrinsic Safety
Certificate UL-BR 13.0584X
Standards ABNT NBR IEC60079-0:2013, ABNT NBR IEC60079-11:2013
Markings
Table 4-8: Input Parameters
Parameter
Voltage U
Current I
Power P
i
Capacitance C
Quick Start Guide
ABNT NBR IEC 60079-26:2016
Ex db IIC T6...T4 Ga/Gb, T6(–60 °C ≤ Ta ≤ +70 °C), T4/T5 (–60
°C ≤ Ta ≤ +80 °C)
HART: Ex ia IIC T5/T4 Ga, T5(–60 °C ≤ Ta ≤ +40 °C), T4 (–60 °C ≤
Ta ≤ +70 °C)
Fieldbus/PROFIBUS: Ex ia IIC T4 Ga (–60 °C ≤ Ta ≤ +60 °C)
HART
30 V
i
200 mA
i
0.9 W
0.012 µF
i
Quick Start Guide
Fieldbus/PROFIBUS
30 V
300 mA
1.3 W
0 µF
35