2.5.1
Verify configuration with a Field Communicator
You must install a Rosemount 3051 DD on the Field Communicator to verify
configuration.
Table 2-2
sequences using legacy DD's, contact your local Emerson representative.
Note
Emerson recommends installing the latest DD to access the complete
functionality. Visit
updating the DD library.
Verify device configuration using the Fast Key sequences in
Table 2-2: Device Revision 9 and 10 (HART 7), DD Revision 1 Fast Key Sequence
A check (✓) indicates the basic configuration parameters. At minimum, verify these parameters
as part of configuration and startup.
Function
Alarm and saturation levels
Damping
Range values
Tag
Transfer function
Units
Burst mode
Custom display configuration
Date
Descriptor
Digital to analog trim (4-20 mA output)
Disable configuration buttons
Rerange with keypad
Loop test
Lower sensor trim
Message
Scaled D/A trim (4-20 mA output)
Sensor temperature/trend (3051S)
Quick Start Guide
shows Fast Key sequences for the latest DD. For Fast Key
Emerson.com/Field-Communicator
for information on
Fast Key sequence
HART 7
2, 2, 2, 5, 7
2, 2, 1, 1, 5
2, 2, 2
2, 2, 7, 1, 1
2, 2, 1, 1, 6
2, 2, 1, 1, 4
2, 2, 5, 3
2, 2, 4
2, 2, 7, 1, 4
2, 2, 7, 1, 5
3, 4, 2
2, 2, 6, 3
2, 2, 2, 1
3, 5, 1
3, 4, 1, 2
2, 2, 7, 1, 6
3, 4, 2
3, 3, 3
Quick Start Guide
Table
2-2.
HART 5
2, 2, 2, 5, 7
2, 2, 1, 1, 5
2, 2, 2
2, 2, 7, 1, 1
2, 2, 1, 1, 6
2, 2, 1, 1, 4
2, 2, 5, 3
2, 2, 4
2, 2, 7, 1, 3
2, 2, 7, 1, 4
3, 4, 2
2, 2, 6, 3
2, 2, 2, 1
3, 5, 1
3, 4, 1, 2
2, 2, 7, 1, 5
3, 4, 2
3, 3, 3
19