Table 2-3: LOI Button Operation
Button
Left
Right
Figure 2-17: LOI Menu
2.5.3
Switch HART revision mode
If the HART configuration tool is not capable of communicating with HART
Revision 7, the Rosemount 3051 loads a generic menu with limited
capability. To switch the HART revision mode from the generic menu:
Go to Manual Setup → Device Information → Identification → Message.
To change to HART Revision 5, enter
To change to HART Revision 7, enter
Quick Start Guide
to confirm external button functionality.
No
Yes
SCROLL
ENTER
in the Message field.
HART5
in the Message field.
HART7
Quick Start Guide
Assign PV
HART Revision
21