Quick Start Guide
Note
A weep hole has been designed into the transmitter for safety and
leak detection. If fluid begins to leak from the weep hole, isolate the
process pressure, disconnect the transmitter, and reseal until the
leak is resolved.
2.2
Consider housing rotation
To improve field access to wiring or to better view the optional LCD display:
Figure 2-13: Housing Rotation
A. Housing rotation set screw (5/64-in.)
Procedure
1. Loosen the housing rotation set screw using a 5/64-in. hex wrench.
2. Rotate the housing clockwise to the desired location.
3. If the desired location cannot be achieved due to thread limit, rotate
the housing counterclockwise to the desired location (up to 360°
from thread limit).
4. Retighten the housing rotation set screw to no more than 7 in-lb
when it reaches the desired location.
2.3
Set the switches
Use the following procedure to change the switch configuration:
Set Simulate and Security switch configuration before installation as shown
in
Figure
The Simulate switch enables or disables simulated alerts and simulated
AI Block status and values. The default Simulate switch position is
Enabled.
The Security switch allows (unlocked symbol) or prevents (locked
symbol) any configuration of the transmitter.
14
A
2-14.
January 2020