www.pulsar.pl
Voltage adjustment range
Ripple
Battery charge current
Space for battery
Approximate backup time
Short-circuit protection SCP
Overload protection OLP
Battery circuit protection SCP and reverse
polarity connection
Surge protection
Overvoltage protection OVP
Excessive discharge protection UVP
Tampering protection system:
- TAMPER – indicating unwanted opening of the
PSU's enclosure
LED indication:
- AC diode indicating AC power status
- AUX diode indicating DC power status at PSU
output
F1÷F9
Mechanical parameters (tab. 4)
Dimensions
Fitting battery
Fixation
Net/gross weight
Enclosure
Closing
Connectors
Notes
Operation safety (tab. 5)
Protection class EN 62368-1
Protection grade EN 60529
Electrical strength of insulation:
- between input and output circuits of the PSU
- between input circuit and protection circuit
- between output circuit and protection circuit
Insulation resistance:
- between input circuit and output or protection circuit
Operating parameters (tab. 6)
Operating temperature
Storage temperature
Relative humidity
Vibrations during operation
PSDCB09129C
W=300, H=300, D+D
=105+8 [+/- 2mm]
1
W
=305, H
=305 [+/- 2mm]
1
1
185x170x90mm (WxHxD) max
see figure 3
2.7 / 2.85 [kg]
Steel plate, DC01 0,7mm colour: RAL 9003
Cheese head screw x 2 (at the front), lock assembly possible
Power supply: Φ0,63-2,50 (AWG 22-10)
OutputsФ0,41÷1,63 (AWG 26-14),
Battery output BAT: 6,3F-2,5
TAMPER output: wires
The enclosure does not adjoin the assembly surface so that cables can be led.
-10ºC...+40ºC
-20ºC...+60ºC
20%...90%, without condensation
unacceptable
5
13,5 – 14 V
100 mV p-p max.
1 / 4A (± 5%)
17Ah/12V (SLA)
2h 30min
LB9 STRIP
9x glass fuse
105 ÷ 150% of power supply, automatic recovery
glass fuse T10A/250V
varistors
>19V (automatic recovery)
U<9,5V (± 5%) – disconnect of connection battery
- microswitch, NC contacts (enclosure closed),
0,5A@50 V DC (max.)
- red, normal status: permanently illuminated, failure: off
- green, normal status: permanently illuminated,
failure: off
F 1A/250V
I (first)
IP20
2500 V AC min.
1500 V AC min.
500 V AC min.
100 MΩ, 500 V DC
Need help?