en | Commissioning
5.1.1

Testing the power supply

1.
2.
3.
4.
5.
5.1.2

Testing the Conventional and LSN Functions

1.
2.
5.1.3

Testing the Addressing/Activation

1.
2.
3.
4.
5.2

Panel controller firmware

A variety of firmware versions is available. Depending on the version number, a firmware is
suitable for a certain hardware platform:
2022-07 | 5.0 | F.01U.378.910
Measure the voltage of the batteries.
The target values are12.0 V to 14.1 V, or 24 V to 28.2 V.
Test the power failure function
Remove the fuse and make sure that the failure of the power supply is indicated on the
display.
Make sure that the time limit for failure of the power supply is set to around 25min (in
the configuration).
Restore the power supply.
Once the fire alarm system is reconnected to the power supply, it automatically goes into
standby mode, and the power supply failure display disappears.
Test the battery failure function:
Remove the cables between the batteries and the BCM-0000-B module.
Make sure that the time limit for failure of the batteries is set to around 25min (in the
configuration).
Indication of battery failure can be delayed by up to 15min.
Reconnect the cables between the batteries and the BCM-0000-B module.
Once the connection with the batteries has been restored, the battery failure display
must be reset manually.
Testing a conventional/LSN loop:
Disconnect the conventional/LSN loop by detaching the cable connection to the
corresponding functional module.
Failure of the conventional/LSN loop must be indicated on the display.
Restore the connection between the conventional/LSN loop and the corresponding
functional module and reset the error message. Now test all automatic and manual
detectors.
Testing a conventional/LSN stub:
Disconnect the conventional/LSN stub by detaching the cable connection to the
corresponding functional module.
Failure of the conventional/LSN stub must be indicated on the display.
Restore the connection between the conventional/LSN stub and the corresponding
functional module and reset the error message. Now test all automatic and manual
detectors.
Test the activation of the transmission devices (TD/DACT/TSN/GSM/X25/X31) by
triggering the corresponding assigned detector.
Test the activation of the transmission devices (TD/DACT/TSN/GSM/X25/X31) by
initiating the corresponding fault.
Test the activation of extinguishing systems, door controls etc.
Test all internal alarm signaling equipment (e.g. audible and visual notification
appliances).
System manual
AVENAR panel
Bosch Sicherheitssysteme GmbH