en | Maintenance and service
Front door
Bosch provides no front door for AVENAR panel.
Redundant panel controller
Firmware and configuration
To reuse the configuration, follow these steps:
1.
2.
3.
4.
5.
6.
7.
8.
9.
Battery autonomy
2022-07 | 5.0 | F.01U.378.910
Check if a device with an RS232 interface, for instance printer, is connected to the panel
controller.
When required, order an IOS 0232 A or IOS 0020 A.
Do not operate the system with a front door.
Remove the front door before installing an AVENAR panel controller. Otherwise, the
system can overheat because the air vents are blocked.
Always replace the master and slave panel controller when upgrading FPA-5000 with a
redundant panel controller to AVENAR panel 8000. The panel will not work properly when
an AVENAR panel and FPA-5000 panel controller are combined in one panel!
When a premium license is required, make sure that the redundant panel controller
contains a premium license as well. This way the interfaces to the building management
system, hierarchy panel and voice alarm system will remain available when the slave panel
controller takes over control.
AVENAR panel 8000 is not compatible with the CRP 0000 A cable set. Use an FPE-8000-
CRP cable set instead.
The cable to the slave panel controller needs to be connected directly at the OUT of the
last long rail.
Do not use the second short rail anymore. Refer to installation guide for FPE-8000-CRP
Cable set redundant panel controller.
The panel controller, which needs be replaced, is perhaps still running on a firmware V1.x
or V2.x.
When AVENAR panel needs be integrated in a panel network combined with FPA panel
controllers type B and C, it is mandatory to use the compatible firmware V3.x. All panel
controllers (AVENAR panel and FPA) needs to be upgraded to an identical V3.x firmware.
Use panel firmware V4.x when the system consists exclusively of AVENAR panel and
AVENAR keypad.
Open FSP-5000-RPS.
Click with the right mouse button on the account.
Select Upgrade to followed by AVENAR panel V3.x or AVENAR panel V4.x.
It is recommend to select Copy and Upgrade.
A new firmware V3.x or V4.x account is created.
Open the configuration of the new account.
Select the nodes which are equipped with an AVENAR panel controller.
Change the node type to AVENAR panel and select Apply.
Load the configuration.
Perform a complete functional test of the system.
Compared with an MPC-xxxx-C, an AVENAR panel controller has a slightly lower power
consumption when configured with an identical configuration. In this case, the Ethernet
ports 3 and 4 are not used and must be disabled in the configuration. Only in this case,
the power battery autonomy remains on the previous level.