Bosch AVENAR panel System Manual page 14

Table of Contents

Advertisement

14
en | AVENAR panel series
Additional annunciator modules, each with 16 red and 16 yellow LEDs are available to indicate
a larger number of self-defined alarms, faults or deactivations.
Smart Safety Link
Smart Safety Link is the most reliable and secure interface to combine a fire detection and a
voice alarm system (VAS). Smart Safety Link offers exceptional flexibility and options for
expandability.
The bi-directional data communication establishes a supervised connection between the fire
detection panel and the VAS. Both the fire panel and the VAS indicate a fault message when
the connection is interrupted. In case of an interrupted connection, the user can start the
evacuation of the complete building manually by using a call station of the VAS. An
interruption of the interface does not lead to an automatic evacuation of the building. When
the interface is re-established, the fire panel automatically re-synchronizes the current alarm
state with the VAS. In case of a fire condition, the fire panel can automatically start voice
announcements using virtual VAS triggers that are activated by rules which are configured in
FSP-5000-RPS. The fire panel generates a supervisory message when an evacuation event is
started from the VAS. A malfunction on the VAS will generate a fault message on the user
interface of the fire panel.
For the connection to the PRAESENSA, the Praesideo and the PAVIRO voice alarm systems, an
Ethernet interface is used. Smart Safety Link to PRAESENSA features TLS encryption which
guarantees a high level of data protection. The Ethernet interface provides up to 244 freely
configurable virtual VAS triggers. The Plena VAS uses an RS232 interface of the IOS 0020 A or
IOS 0232 A communication module. The Plena VAS can be configured with up to 120 virtual
VAS triggers.
Operator management
The system can have up to 200 different registered operators. Login is permitted with a user
ID and an 8-digit pin code.
There are four different authorization levels. Depending on the authorization level it is possible
for the operator to do certain functions according to EN54-2.
Languages
The operator can change the language of the user interface. A quick user guide for each
language is available. Following languages are included in the package: English, German,
Bulgarian, Croatian, Czech, Danish, Dutch, Estonian, French, Greek, Hungarian, Italian, Latvian,
Lithuanian, Polish, Portuguese, Romanian, Russian, Serbian, Slovak, Slovenian, Spanish,
Swedish and Turkish.
The quick user guides of following languages are available only online at
www.boschsecurity.com: Hebrew and Ukrainian.
Operation and processing of messages
For operating the panel, an 8 inch touch pad as input medium is put upon the display. There
are 6 buttons with fixed functionality as well as 3 programmable function keys.
Examples for the assignment of the function keys:
Each function key has a virtual status indicator.
At any time, an operator with sufficient user rights can activate each evacuation zone and each
output connected to fire protection equipment via the user interface.
The panel controller features
2022-07 | 5.0 | F.01U.378.910
Set the panel controller to day mode, set the panel controller to night mode
Enable detection points or outputs, disable detection points or outputs
Set standard sensor sensitivity, set alternative sensor sensitivity
2 CAN interfaces (CAN1/CAN2) for networking
System manual
AVENAR panel
Bosch Sicherheitssysteme GmbH

Advertisement

Table of Contents
loading

Table of Contents