en | Planning
L [m]
3200
3000
2800
2600
2400
2200
2000
1800
1600
1400
1200
1000
20mA
800
10mA
600
7,5mA
400
200
0
0
10
20
30
Figure 3.4: Diagram for determining the maximum achievable cable length: LSN improved elements with LSN 1500 A
L =
N =
a =
b =
3.9

Configuration with BCM-0000-B modules

AVENAR panel 8000 can be powered by up to 8 BCM-0000-B battery controller modules, each
with its own UPS 2416 A power supply unit. Current consumption is equally distributed among
all battery controller modules.
Notes
Configuration with 1 to 4 BCM-0000-B modules in wall mounting housings
2022-07 | 5.0 | F.01U.378.910
a
5mA
4mA
3mA
40
50
60
70
80
90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250
cable length in meters
number of LSN improved elements
Bus dynamic limit
maximum possible number of LSN improved elements = 254
The 24 V switch outputs may not be connected in parallel.
The total current for all connected components including the battery charge current may
not exceed 6 A.
The batteries connected to the BCM must all be of the same type and have identical
electrical properties.
The cable length at the switch outputs for faults may not exceed 3 meters.
The cables for the switch outputs for faults may only be routed inside the housing.
Up to 2 BCM-0000-B modules on short panel rail
Maximum 2 BCM-0000-B modules at the end of the long panel rail
Each BCM-0000-B module requires one UPS 2416 A power supply unit.
2,5mA
2mA
System manual
AVENAR panel
0,265mA
0375mA
0,5mA
0,7mA
1,25mA
1,5mA
1mA
N
Bosch Sicherheitssysteme GmbH