AVENAR panel
3.2

Detection points

Each element or input that can trigger an alarm counts as an detection point. One stand-alone
panel manages up to 4096 detection points. A panel operated in a network is limited to 2048
points.
All elements and inputs that do not use the Input type in the Message type setting are
regarded as detection points. Therefore, all elements and inputs for which one of the
following settings is programmed as the Message type are regarded as detection points:
Only some of these message types are available for selection depending on the element type.
The elements and inputs that can trigger an alarm include all manual and automatic detectors,
as well as the modules and interface modules listed below on the basis of the available inputs.
Modules
CZM 0004 A
IOP 0008 A
RMH 0002 A
ENO 0000 B
FPP‑5000‑TI
Interface Modules
FLM-420/4CON
FLM-420-I8R1
FLM-420-I2
FLM-420-O8I2
FLM-420-O1I1
FLM-420-RHV
FLM-420-RLE-S
Bosch Sicherheitssysteme GmbH
Cable length of up to 3000 m
As stipulated by EN 54-2, panels with more than 512 detectors and manual call points
must be equipped with a redundant panel controller. Combined with an AVENAR panel
8000, an AVENAR keypad 8000 can be used as a redundant panel controller.
Fire
Internal fire
Supervisory
Multi-criterion
Smoke
Fault
Heat
Water
Detection Points
Up to 4 (1 detection point per zone)
Up to 8 (1 detection point per monitored input)
Up to 2
requires 1 detection point only if a FSE release element is
connected and programmed using the FSP-5000-RPS
programming software
2
Detection Points
Up to 2
Up to 8
Up to 2
Up to 2
Up to 1
Up to 2
Up to 2
System manual
Planning | en
2022-07 | 5.0 | F.01U.378.910
29