en | AVENAR panel series
Module
ANI 0016 A
BCM-0000-B
CZM 0004 A
ENO 0000 B
FPE-5000-UGM Module interface to
IOP 0008 A
IOS 0020 A
IOS 0232 A
LSN 0300 A
Notice!
i
Safety Systems Designer can be used to plan fire alarm systems that conform to the relevant
limits (e.g. in terms of cable length and power supply).
Notice!
Safety Systems Designer for fire alarm systems enables the system dimensions, the energy
i
requirements and the quantity and prices of the elements required to be estimated at each
different phase in the planning process.
The software is designed for planners and engineering offices that want to produce a
quotation for a fire alarm system.
2022-07 | 5.0 | F.01U.378.910
Functional modules are independent encapsulated units. They are placed into a slot of a
panel rail. The power supply and the data traffic with the panel are therefore provided
automatically. The module is identified by the panel with no further settings and operates
in the default operating mode (plug and play).
Wiring to external components is performed using compact connector/screw terminals.
After a replacement, only the connectors need to be reinserted, there is no need for
extensive rewiring.
Description
Annunciator module Indicating system statuses, with 16 red and 16
Battery controller
module
Conventional zone
module
External notification
module
UGM
Input-output module Individual displays or flexible connection of various
Communication
module, 20mA
Communication
module, RS232
LSN bus module
300mA
Fire brigade peripheral module
A fire brigade peripheral module is connected via FPE-5000-UGM or via IOS 0020 A
functional module. The fire brigade peripheral module FMF-ADP-TTY connects fire service
devices e.g. a Fire service operating panel or a Fire brigade information center to the fire
panel.
Function
yellow freely programmable LEDs
Controlling the power supply to the panel and the
battery charge level
Connecting conventional peripheral devices using
four monitored conventional lines
Connecting fire service equipment complying with
DIN 14675
Connection to UGM systems
electrical devices, with 8 independent digital inputs
and 8 open collector outputs
With S20 and RS232 interfaces
Connection of two devices using two independent
serial interfaces, e.g. Plena or a printer.
Connection of an LSN loop with up to 254 LSN
improved elements or 127 LSN classic elements at a
maximum line current of 300 mA
System manual
AVENAR panel
Bosch Sicherheitssysteme GmbH