Installation; General Information - Bosch AVENAR panel System Manual

Table of Contents

Advertisement

AVENAR panel
4

Installation

Consider the general information and follow the rough installation sequence. Subsequently
you find two specific installation sequences:
For information on the installation of each component, refer to the Installation guide, which is
included in the delivery and also available at www.boschsecurity.com.
4.1

General information

Warning!
Live components and stripped cable! Risk of injury from electric shock. The system must be
!
current-free during connection work.
Warning!
Electrostatic discharge.
!
The standard precautions for CMOS technology must be taken when handling PC boards.
Warning!
Risk of overheating
!
Bosch provides no front door for this system. You are not allowed to operate the system with
a front door. Otherwise, the system can overheat, because the air vents are blocked.
Environmental Conditions
Positioning
Bosch Sicherheitssysteme GmbH
CPH 0006 A, fully configured panel
HCP 0006 A, fully configured panel
The fire panel may only be installed and commissioned by trained specialist personnel.
Only use installation materials recommended by Bosch. Otherwise, interference
resistance cannot be guaranteed.
Connection conditions set down by the regional authorities and institutions (police, fire
service) must be observed.
Assembly and operation of the fire panel must be carried out in a clean and dry indoor
location.
Permissible relative humidity: max. 95 % at 25°C, non-condensing
To ensure optimum battery service life, the panel should only be operated at sites with
normal room temperatures.
Do not operate devices showing condensation.
Operating and display elements should be positioned at eye level.
The distance between the upper edge of the housing and the center of the panel
controller display is around 11 cm. For example, if the eye level required is 164 cm, the
housing upper edge installation dimension is 175 cm.
For frame installation housings, a clearance of at least 230 mm is required to the right of
the last housing to swivel out the installed housing (e.g. for connection, maintenance or
service).
Sufficient space should be left below and next to the panel for any possible extensions,
e.g. for an additional power supply or an extension housing.
System manual
Installation | en
2022-07 | 5.0 | F.01U.378.910