13.10 Analog Ac Current Input (Aci) Card Wiring; Figure 13-8: Aci Card Wiring & Cabling Diagram - Veesta World V-RTU2000 Series Technical Information

Table of Contents

Advertisement

V-RTU2000 Series
Veesta - Remote Terminal Unit
Technical Specification Manual

13.10 Analog AC Current Input (ACI) Card Wiring

100 mm
DB9 M
RS-232
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
 Front Panel: 1 LED Run Indicator, 1 LED Pickup Indication
 Rear Panel: 4 input points: CT1 ~ CT4, configurable for 3 modes.
160 mm
J2
J3
J4
Figure 13-8: ACI Card Wiring & Cabling Diagram
In the VR-2745 ACI Card, you have three methods of AC current
measurement wiring signals:
 Mode 1: 6xWire 3xCT or 3xPhase Measurement Mode, it is for
normal AC 3x phase measurement in 6 wire individual mode. For
setup this mode you must un-jumper J2,J3 and J4.
 Mode 2: 8xWire 4xCT Measurement Mode, it is for measuring 4
independent AC current inputs. Each CT individually metering
current and wired to the back plane of Card. For setup this mode
you must un-jumper J2, J3 and J4 in back of Card.
 Mode 3: 4xWire 3xPhase Measurement Mode, it is for normal
current measurement of 3x Phase AC circuit. Please be informed
that in this case the common of CTs also can be measured in
Card as neutral/common current. For setup this you must jumper
J2, J3 and J4 in back of Card. (Mode 3 is default mode).
Chapter 13 - Wiring & Cabling
Source
Load
Source
0
0
90
180
Load
M
FM
Source
Load
Source
Load/Com
96-Pin DIN
Connector
Mode 1
Mode 2
Mode 3
CT1A-S
CT1-S
CT1A
CT1A-L
CT1-L
-
CT2B-S
CT2-S
CT2B
CT2B-L
CT2-L
-
-
-
-
-
-
-
CT3C-S
CT3-S
CT3C
CT3C-L
CT3-L
-
-
CT4-S
-
-
CT4-L
CT-Com