Digital Output (Do) Card Wiring; Figure 13-5: Do Card Wiring & Cabling Diagram - Veesta World V-RTU2000 Series Technical Information

Table of Contents

Advertisement

V-RTU2000 Series
Veesta - Remote Terminal Unit
Technical Specification Manual
13.7

Digital Output (DO) Card Wiring

100 mm
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
 Front Panel: 8 LED Indicator
 Rear Panel: 8 output points: CH1 ~ CH8, 1 common point: COM,
1 frame ground point: FG.
160 mm
J2
Straps in
back of PCB
J3
Figure 13-5: DO Card Wiring & Cabling Diagram
In the VR-2736A, you have two methods of common wiring signal of
8xDO relays:
 COM1, it is protected by auto-resettable fuse in case of any short
circuit of DO side. This auto-resettable fuse can handle up to 60V
between contacts of DO relays. For setup this you must strap J2
and J3.
 COM2, it is protected by 8A Fuse, but it is not auto-resettable, in
case of any damage caused by short circuit you must replace the
fuse on the card. For setup this type you must strap J2 and J3.
 Independent COM1 & COM2, in this case two channels of CH1,
CH2 can be protected by auto-resettable fuse by COM1, and
CH3~CH8 outputs with COM2 via main execution relay with 8A
fuse. For setup this you must strap J2 and un-strap J3. For
example if you want to have internal test relay circuit, so test rely
used for CH1,CH2 by independent common signal of field.
Chapter 13 - Wiring & Cabling
0
0
90
180
M
FM
96-Pin DIN
Connector
VR-2736A
COM1
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
COM2
Page 77 of 90