V-RTU2000 Series
Veesta - Remote Terminal Unit
Technical Specification Manual
Chapter 11 - Universal Intelligent AC Power Meter Unit
11.1
General
11.2
ACUP Card
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
Chapter 11 - Universal Intelligent AC Power Meter Unit
In principle design, the VR-2760 Power Meter from V-RTU2000
Series of products is of intelligent Power Meter which is with high-
precision intelligent digital power transducer, having capacity to
measure the input signals of 3 currents (CT) and 3 voltages (PT), can
directly measure up more over 100 kinds of power parameters. This
unit is equipped with 2 sets of CPU comply with its Firmware,
enhancing analog sampling and digital computation function. It
connects to CPU Card through RS-485 communication interface
which is on the first group of backplane. The hardware is designed in
standard DIN rack mounting by plug-in type for meeting the DIN
specification, under in one-switching V.S linking with external CT
terminal. Other terminals include 3 PT, working power and 2
communication interfaces (COM1 and COM2) for transmitting to the
backplane terminal for actual application through under 96-Pin DIN
Connector. In design, the analog circuit and digital circuit are
arranged into different circuit board.
The VR-2760 Digital Power Meter Unit is microprocessor-based
instrument intended for power and energy measurement. Additional
functionality option to provide control function as synchro check, The
VR-2760 is Universal Intelligent Electronic Device (IED) and stores
these measured values and setting parameters in internal registers
for
communication. With the
modularized & plug-in design, and compact size, VR-2760 is very
suitable for Electric Utility Substation Automation application.
The ACUP Card Features:
Current input terminal with automatic shorting mechanism
Over 90 power and energy parameters
Modbus® RTU / DNP3.0 protocol
4-AC current inputs, 5A or 1A (specified when ordering)
4-AC voltage inputs, maximum 300V
True RMS conversion
32 sample points per cycle
Instant maximum and minimum logger
Waveform capture
200 event logs for all measured quantities
features, high accuracy, fully
Page 59 of 90