Chapter 7 - Analog Input Unit; General; Ai Card - Veesta World V-RTU2000 Series Technical Information

Table of Contents

Advertisement

V-RTU2000 Series
Veesta - Remote Terminal Unit
Technical Specification Manual
Chapter 7 -
7.1

General

7.2

AI Card

All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
Analog Input Unit
The Analog Input Unit of V-RTU2000 Series comprises three card
types. Each AI cards board provides 4 Differential Channels
(CH1+/CH1- ~ CH4+/CH4-) and 2 Shielding Points (S1, S2). Listed
below is the card types provided by the V-RTU2000 Series:
 AI Card (+/-1mA): Analog Input Card, 4 Differential Channels /
Card, Input Range +/-1mA.
 AI Card (4~20mA): Analog Input Card, 4 Differential Channels /
Card, Input Range 4~20mA.
 AI Card (-5 ~ +5V): Analog Input Card, 4 Differential Channels /
Card, Input Range +/- 5VDC.
For application, AI Card is normally used to measure output signals
from power transducer of Watt, Var, Voltage, Current, Temperature,
Position, Resistance, as to monitor the operation status of power
system, including the measured values of current, temperature and
Tap position.
Analog Input Card is an intelligent IO Card, which is used to measure
the output values of power transducer as to monitor the status for
power system, including current, temperature and Tap position. It
contains CPU comply with its Firmware, it also provides interface and
converting circuit required for analog input. It connects to CPU Card
through LIOC RS-485 communication interface, the DATA & /DATA
Communication Signal is linked by the backplane without additional
wirings. The external connection contains 4 Differential Input
Channels (Ch1+/CH1- ~ CH4+/CH4-) and 2 Shielding (S1, S2),
which are transmitted through 96-Pin DIN Connector to 10-Pin
terminal on the backplane for actual application. In design, the
analog and digital circuits are isolated using differential input type to
provide stronger restraining power to press down the common mode
noise.

Chapter 7 - Analog Input Unit

Page 48 of 90