11.2.2 Fault Current Detection Function - Veesta World V-RTU2000 Series Technical Information

Table of Contents

Advertisement

V-RTU2000 Series
Veesta - Remote Terminal Unit
Technical Specification Manual
Parameter Digits
Vx3
4
9.9.9.9. V/KV
Ax3
4
9.9.9.9. A/KA
Watts
4
9.9.9.9. W/KW/MW/GW
Vars
4
9.9.9.9. Var/KVar/MVar/GVar
VA
4
9.9.9.9. VA/KVA/MVA/GVA
PF
4
1.000
WH
7
9.9.9.9.9.9.9. WH/KWH/MWH/GWH
VarH
7
9.9.9.9.9.9.9. VarH/KVarH/MVarH/GVarH
A0
4
9.9.9.9. A/KA
AFx3,AF0
4
9.9.9.9. A/KA
Hz
4
70.00
Angle
4
359.9 DG
*
Accuracy performance range for WH/VarH, PF
(-10 to 50 )
PF = Cosθ for WH ; PF = Sinθ for VarH
Voltage
60V ; Current
-1
***
0.2° ± SIN
(0.02 x PF)

11.2.2 Fault Current Detection Function

11.2.2.1
Fault-Based-Curve
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
Chapter 11 - Universal Intelligent AC Power Meter Unit
Table 11-1: VR-2760 Programmable measurements/accuracy/display readouts
Display (maximum)
0.5
20% of rating
One user programmable Fault-Based-Curve can be stored in the
ACUP Card Model VR-2760. This can be used for time over-current
detection in the same as IEC, ANSI curves. The custom Fault-Based-
Curve has set-points for entering times to fault at the following
current levels (I/Ipu): 1.00 to 1.20 in steps of 0.05 and 1.20 to 6.00 in
steps of 0.4, and 6.0 to 16.0 in steps of 2.0. The ACUP then converts
these points to a continuous curve by linear interpolation between
data points.
(I/Ipu)
Fault
Time
1 . 00
0-65535
1 . 05
0-65535
1 . 10
0-65535
1 . 15
0-65535
1 . 20
0-65535
1 . 60
0-65535
2 . 00
0-65535
2 . 40
0-65535
Accuracy
option=N option=A
0.15% fs 0.25% fs
0.15% fs 0.25% fs
0.25% fs 0.25% fs
0.25% fs 0.25% fs Var1
0.25% fs 0.5% fs
0.25% fs 0.25% fs PF1
* 0.25% rd/
** 0.5% rd
PF
* 0.25% rd/
** 0.5% rd
PF
0.5% fs 0.25% fs
None
1% fs
0.03% rd 0.03% rd
***
***
**
Accuracy performance range for WH/VarH, PF
(-10 to 50 )
PF = Cosθ for WH ; PF = Sinθ for VarH
Voltage
60V ; Current
(I/Ipu)
Fault
Time
2 . 80
0-65535 6 . 00
3 . 20
0-65535 8 . 00
3 . 60
0-65535 10.00
4 . 00
0-65535 12 . 0
4 . 40
0-65535 14 . 0
4 . 80
0-65535 16 . 0
5 . 20
0-65535
5 . 60
0-65535
Phase
Phase
Phase
Total Average
1
2
3
V1
V2
V3
A1
A2
A3
W1
W2
W3
W
Var2
Var3
Var
VA1
VA2
VA3
VA
PF2
PF3
PF
WH
VarH
DG1
DG2
DG3
DG
10% of rating
(I/Ipu)
Fault
Time
0-65535
0-65535
0-65535
0-65535
0-65535
0-65535
Page 63 of 90