Huawei FusionModule 500 Quick Manual page 5

Smart mini data center
Table of Contents

Advertisement

3
Exhausting Nitrogen from an Indoor Unit
1. Open the stop valve for the gas pipe
of the indoor unit.
4
Installing an Outdoor Unit
To avoid a fire disaster, install an outdoor unit in a dry and well-ventilated place without
flammable gas leakage.
Select a place away from direct sunlight and radiation from other heat sources. If the
sunlight or heat radiation cannot be avoided, cover the outdoor unit.
Do not install an outdoor unit in a place with much salt or corrosive gas.
When installing the outdoor unit, ensure that the air intake vent and air exhaust vent of the
condenser are not dirty or blocked. Install an outdoor unit in a clean area that is away from
residential areas.
At a high place with strong winds, install the outdoor unit against a wall to ensure the
normal operating of fans. Install a baffle plate when necessary to prevent the outdoor unit
from toppling in strong winds.
Install an outdoor unit against a wall if possible. If the site conditions cannot meet the
requirements and the local outdoor temperature may be below –10°C, install a baffle plate
by referring to the space requirements. The baffle plate height and width should be greater
than or equal to the outdoor unit height and width, respectively.
If the site installation environment is complicated and the preceding conditions are not met,
contact Huawei technical support.
2. Loosen the needle valve nut, connect a rubber hose
and a pressure gauge, and slowly exhaust nitrogen.
3. After the airflow sound disappears, reinstall the
needle valve nut.
(1) Pressure gauge (2) Gas pipe needle valve
(3) Liquid pipe needle valve